Question

Three single phase transformers having a 15:1 ratio are wye-connected to a 2400 V three phase...

Three single phase transformers having a 15:1 ratio are wye-connected to a 2400 V three phase line as a step-down transformer. What is the line voltage of each transformer? What is the secondary voltage of each transformer if they are delta connected to the same line?

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is rated at 1000 kVA and has a step-down ratio of 8:1. The bank supplies a balance load having a power factor of 0.8 lag with a load current of 70 A. Assume ideal transformer, determine. The primary line and phase voltages The secondary line and phase voltages The secondary line and phase currents The apparent and active power at the load Total kVA capacity...
A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has...
A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has synchronous reactance of X~ = 1.0 fl . The generator is connected to a threephase delta-wye connected step-down transformer that is constructed from three individual single-phase transformers. Each the single-phase transformers has rated power of 200 kVA has a turns ratio of 4:1 where the rated primary voltage of 8.0 kV and a rated secondary of 2.0 kV and a per-unit series reactance of...
A wye connected three-phase source is delivering a line voltage of 480 V at a line...
A wye connected three-phase source is delivering a line voltage of 480 V at a line current of 25 amperes. Find a) the phase voltage b) the phase current c) the line voltage d) the line current e) the total power delivered.
A balanced wye-connected three-phase source has line-to-neutral voltages of 400 V rms. - Find the rms...
A balanced wye-connected three-phase source has line-to-neutral voltages of 400 V rms. - Find the rms line-to-line voltage magnitude. - If this source is applied to a wye-connected load composed of three 33 Ω resistances, find the rms line-current magnitude. - If this source is applied to a wye-connected load composed of three 33 Ω resistances, find the total power delivered.
The transformer is protected by a differential relay. The relay is connected to three phase transformer,...
The transformer is protected by a differential relay. The relay is connected to three phase transformer, 50 MVA, 22 kV/33 kV delta – star connection. The relay is connected in delta. The current transformer ratio is 1500/5 Amp at the lower voltage and 1000/5 Amp at the high voltage. Calculate the primary and secondary current of the relay and it’s the primary turns. State any assumption.
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is connected to a three phase Y-Y transformer T1 which feeds a 132 kV 10 miles transmission line having an impedance per phase of 2 + j5 ?/mile. At the receiving end of the transmission line is a Y-Y step down transformer T2. Three loads are connected to the secondary side of the transformer T2. Loads are as follows: Load#1 40 MVA at 0.8 pf...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V,...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V, 50 Hz, io = 1.2%; ukN = 6%, idle losses 2450 W, rated copper losses of power 14500 W; Dy5. a) Calculate primary and secondary line and phase currents. b) Secondary at 75% load in power factor with 0.85 inductance and 0.85 capacity calculate the voltage separately. Compare and interpret the results. capacity at what time of day can the upload be seen? To...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V,...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V, 50 Hz, io = 1.2%; ukN = 6%, idle losses 2450 W, rated copper losses of power 14500 W; Dy5. a) Calculate primary and secondary line and phase currents. b) Secondary at 75% load in power factor with 0.85 inductance and 0.85 capacity calculate the voltage separately. Compare and interpret the results. capacity at what time of day can the upload be seen? To...
A balanced ?-connected load has an impedance of 60+ j45 ? per phase. The load is...
A balanced ?-connected load has an impedance of 60+ j45 ? per phase. The load is fed through a line having an impedance of 0.8+ j0.6 ? per line. The phase voltage at the terminals of the load is ???????? = 480 ?? . The sequence is positive. Use AB v as the reference at the load. The source is required to be calculated for either Wye or Delta connection. a) Draw the 3-phase system b) Draw the a-phase equivalent...
The line current of a three-phase engine in delta configuration is 25 A, connected to a...
The line current of a three-phase engine in delta configuration is 25 A, connected to a supply network with a line voltage of 240 V and absorbing a power of 15 kW. The efficiency of the engine is 90%. Taking as a reference of line voltages V1= V∠0º, and a direct sequence, find: a) The phasors of the line voltages b) The phasors of the line and phase currents c) The reactive and apparent power d) The mechanical power (at...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT