Question

A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is...

A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is connected to a three phase Y-Y transformer T1 which feeds a 132 kV 10 miles transmission line having an impedance per phase of 2 + j5 ?/mile. At the receiving end of the transmission line is a Y-Y step down transformer T2. Three loads are connected to the secondary side of the transformer T2. Loads are as follows:

Load#1 40 MVA at 0.8 pf lagging

Load #2 15 MVA at 0.75 pf lagging

Load #3 20 MVA at 0.7 pf leading

The transformer ratings are as follows:

Transformer T1: 120 MVA, 13.2/132 kV, XT1 = 12%

Transformer T2: 100 MVA, 138/33 kV, XT2 = 15%

(i) Draw a one-line diagram for the above power system showing all the equipment parameters, loads and the transmission line.

(ii) Using a base of 100 MVA and a voltage base of 33 kV in the load side of the circuit, draw an impedance diagram of the system expressing all the values in per unit.

(iii) If the load voltage is maintained at 33 kV, calculate the current drawn by the load and the current flowing in the transmission line in per unit and actual.

(iv) Calculate the per unit and actual voltage at the generator terminals.

(v) Calculate the per unit and actual voltages at the beginning of the transmission line and at the end of the transmission line.

(vi) Calculate the active and reactive power delivered by the generator in per unit and actual values.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging •...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load at the low voltage side. The load absorbs 5 MVA, 0.7 power factor lagging at line to line voltage 0.9 kV. The transformer has an equivalent reactance 0.05 Ω/phase. Assuming 10 MVA and 1 kV as base value, draw the per unit diagram for the system. Find the Line to Line voltage at the primary side of the transformer. b) A three-phase synchronous generator...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance of 6.08 Ohms as referred to its high-voltage terminals. The transformer is supplying a load of 375 MVA, with 0.89 power factor lagging at a voltage of 24 kV (line-to-line) on its low-voltage side. It is supplied from a feeder whose impedance is 0.17 + j 2.2 Ohms connected to its high-voltage terminals. The total load in the system remains constant at 375 MVA....
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of 1.33 p.u. The generator achieves rated open circuit voltage at a field current of 325 A. The generator is connected to a network with an equivalent line-line voltage of 11 kV and an equivalent impedance of 0.17 pu on the generator base. The generator is loaded to a real power of 110 MW. a- Find the generated voltage Eaf in p.u. such that the...
A 3? power system consists of a Y-connected source (300 MVA, 23 kV) supplying a Y-connected...
A 3? power system consists of a Y-connected source (300 MVA, 23 kV) supplying a Y-connected load (240 MVA, 230 kV, PF = 0.90 lagging) through a step-up transformer (330 MVA, 23?/230Y kV, X = 0.11 per unit). Take into account the transformer’s phase shift and choose the load terminal voltage VAN as the reference. Use base values of 100 MVA and 230 kV at the load. (a) Find the per-unit load currents (IA, IB, and IC). (b) Find the...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance of 30W and negligible resistance. The generator is connected to an infinite bus at 6.6 KV and 60 Hz. a)Determine the excitation voltage (Ea) when the machine is delivering rated power at o.8 PF lagging. b)The field excitation current is increased by 10% without changing the power input from the prime mover. Find the stator current (Ia), the power factor and the reactive power...
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms...
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms per phase. The machine is connected to kV, 60 Hz bus and is operated as synchronous condenser (synchronous motor at no-load condition) a. For normal excitation (excitation voltage terminal voltage), find the line current. Draw the phasor diagram b. If the excitation is increased to 150% of the normal excitation, find the line current and reactive power delivered or absorbed by the bus. Draw...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance,...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance, Xs = 17.9, and is connected to an infinite bus at rated voltage. If the rotational and electrical losses are negligivle, what is Ia, Ef, delta, theta, Tdrive, Phasor diagram, and power flow diagram (label completely with numerical values for, A) the machine as a generator; the prime-throttle is opened and If is adjusted so that the machine delivers rated kVA, 0.8 pf lagging,...
1- A 69-kV, three-phase short transmission line is 16 km long. The line has a per...
1- A 69-kV, three-phase short transmission line is 16 km long. The line has a per phase series impedance of 0.125 + j0.4375 ohm per km. Determine the sending end voltage, voltage regulation, the sending end power, and the transmission efficiency when the line delivers a. 70 MVA, 0.8 lagging power factor at 64 kV b. 120 MW, unity power factor at 64 kV 2-three-phase, completely transposed 345-kV, 200 km line has two 795,000- cmil 26/2 ACSR conductor per bundle...
1- 30-kV, three-phase transmission line has a per phase series impedance of z = 0.05+j0.45 ohm...
1- 30-kV, three-phase transmission line has a per phase series impedance of z = 0.05+j0.45 ohm per Km and a per phase shunt admittance of y = j3.4x10-6 siemens per km. The line is 80 km long. Using the nominal π model, determine a The transmission line ABCD constants. b Find the sending end voltage and current, voltage regulation, the sending end power and the transmission efficiency when the line delivers 1. 200 MVA, 0.8 lagging power factor at 220...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT