Question

A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has...

A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has synchronous reactance of X~ = 1.0 fl . The generator is connected to a threephase delta-wye connected step-down transformer that is constructed from three individual single-phase transformers. Each the single-phase transformers has rated power of 200 kVA has a turns ratio of 4:1 where the rated primary voltage of 8.0 kV and a rated secondary of 2.0 kV and a per-unit series reactance of 5% (neglect series resistances, core loss resistance and magnetizing reactance). The three-phase transformer supplies power to a three-phase 4-pole induction motor. The induction motor has the following parameters (all values referred to the stator circuit).

R1= 0.500 0 ohms, R2= 0.5000 ohms X1= 1.00 ohms, X2= 1.00 ohm and Xm =10.00 ohm

A)Determine the magnitude of the generator line current when the motor is started from a zero-speed condition

B) What is the line-line (magnitude) of the motor’s stator voltage under the conditions in part ‘a’?

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load at the low voltage side. The load absorbs 5 MVA, 0.7 power factor lagging at line to line voltage 0.9 kV. The transformer has an equivalent reactance 0.05 Ω/phase. Assuming 10 MVA and 1 kV as base value, draw the per unit diagram for the system. Find the Line to Line voltage at the primary side of the transformer. b) A three-phase synchronous generator...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of 1.33 p.u. The generator achieves rated open circuit voltage at a field current of 325 A. The generator is connected to a network with an equivalent line-line voltage of 11 kV and an equivalent impedance of 0.17 pu on the generator base. The generator is loaded to a real power of 110 MW. a- Find the generated voltage Eaf in p.u. such that the...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance of 30W and negligible resistance. The generator is connected to an infinite bus at 6.6 KV and 60 Hz. a)Determine the excitation voltage (Ea) when the machine is delivering rated power at o.8 PF lagging. b)The field excitation current is increased by 10% without changing the power input from the prime mover. Find the stator current (Ia), the power factor and the reactive power...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance,...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance, Xs = 17.9, and is connected to an infinite bus at rated voltage. If the rotational and electrical losses are negligivle, what is Ia, Ef, delta, theta, Tdrive, Phasor diagram, and power flow diagram (label completely with numerical values for, A) the machine as a generator; the prime-throttle is opened and If is adjusted so that the machine delivers rated kVA, 0.8 pf lagging,...
A 42 kVA three-phase synchronous generator with line voltage 4.16 kV at a frequency of 60...
A 42 kVA three-phase synchronous generator with line voltage 4.16 kV at a frequency of 60 Hz, is connected in star configuration. The generator has a winding whose armature resistance is 0.8 Ω and a synchronous reactance of 7.4 Ω, both per phase. Determine the voltage regulation when the power factor is 0.600 lagging.
A three phase Y connected synchronous motor has negligible armature resistance and a synchronous reactance of...
A three phase Y connected synchronous motor has negligible armature resistance and a synchronous reactance of 12 ohm/phase. The motor takes 12,000kW at a line voltage of 13,200V. If the line current is adjusted so that the excitation voltage is 9000V/phase: a. What is the torque angle? b. At what power factor is the motor operating? c. What is its armature current?
A 300MVA, 20KV three-phase generator has a sub-transient reactance of 20%. The generator supplies two parallel...
A 300MVA, 20KV three-phase generator has a sub-transient reactance of 20%. The generator supplies two parallel synchronous motors (M1 and M2) over a 100km transmission line. The line has two transformers T1 and T2 at the beginning and at the end of the line respectively. Both motors are rated at 13.0KV with X"=20%. Motor M1 has a rated input of 100MVA and M2 has a rated input of 50MVA. The transformer T1 is rated 350MVA, 20/230KV and T2 is rated...
A three-phase Wye-connected synchronous generator is rated 3600 rpm, 200kVA, 480V, 60 Hz. The generator’s armature...
A three-phase Wye-connected synchronous generator is rated 3600 rpm, 200kVA, 480V, 60 Hz. The generator’s armature winding resistance is RA = 0.03Ω and the synchronous reactance XS is 0.25Ω. The rotational losses are 6kW, the core losses are 4kW, and the stray losses are 1% of the output real power. The generator is delivering 200kVA power at 0.85 pf lagging at rated voltage. Taking the phase voltage at the output as a reference, answer the following questions. How many poles...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is connected to a three phase Y-Y transformer T1 which feeds a 132 kV 10 miles transmission line having an impedance per phase of 2 + j5 ?/mile. At the receiving end of the transmission line is a Y-Y step down transformer T2. Three loads are connected to the secondary side of the transformer T2. Loads are as follows: Load#1 40 MVA at 0.8 pf...
Please be clear in concept and handwriting. A 20HP, three-phase, Wye-connected synchronous motor is connected to...
Please be clear in concept and handwriting. A 20HP, three-phase, Wye-connected synchronous motor is connected to a 277VAC, 60Hz power supply. At rated conditions, the motor runs at 3600 rpm and presents a 0.85 lagging power factor to the power supply. The per-phase armature reactance is 350m?. Armature resistance is negligible, as are all other sources of power loss. Considering rated conditions, a. draw a single-phase equivalent circuit showing V?, Ea and IA, with values. b. draw a phasor diagram...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT