Question

A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a...

A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a synchronous reactance of 3.0 Ω. Its efficiency at full load is 89% (1 Hp=746 watt).

(a) What is the line current of the generator at rated conditions?

(b) What is the internal generated voltage EA of this motor at rated conditions?

Homework Answers

Answer #1

[question in beginning states generator but part b says motor. solved it for genrator.]

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
The 400 V, 50 kVA, 0.8 power factor leading delta connected synchronous motor has synchronous reactance...
The 400 V, 50 kVA, 0.8 power factor leading delta connected synchronous motor has synchronous reactance of 3-ohm, resistance neglected. It is supplying a 12-kW load with initial power factor of 0.86 lagging. The windage and friction losses are 2.0 kW and the core losses are 1.5 kW. Determine (a) the motor efficiency; the line current; armature current; and excitation voltage. (b) If the flux of the motor is increased by 20 percent determine the excitation voltage; armature current; and...
(360) Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole -connected synchronous motor has 0.9Ω synchronous reactance....
(360) Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole -connected synchronous motor has 0.9Ω synchronous reactance. Friction; wind; core losses and armature resistance are neglected. a) If the motor is operating under magnitude of phase current (ia) (180) Ampere and power factor of 0.6 lagging, 1. Find the input power of motor in hp 2. Find the generated voltage, EA 3. Find the torque and the maximum inducible torque in current state. b) If EA is increased by 18% find,...
410 Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole Triangle connected synchronous motor has 0.9Ω synchronous...
410 Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole Triangle connected synchronous motor has 0.9Ω synchronous reactance. Friction; wind; core losses and armature resistance are neglected. a) If the motor is operating under magnitude of phase current (ia) 230 Ampere and power factor of 0.6 lagging, 1. Find the input power of motor in hp (10p) 2. Find the generated voltage, EA (10p) 3. Find the torque and the maximum inducible torque in current state. (10p) b) If EA is...
A 2300-V, 400-hp, 60-Hz, 1200rpm, Y-connected synchronous motor has a rated power factor of 0.8 leading....
A 2300-V, 400-hp, 60-Hz, 1200rpm, Y-connected synchronous motor has a rated power factor of 0.8 leading. The efficiency of the motor is 90 % at full load. The armature resistance is 0.3 Ω, and the synchronous reactance is 3.55 Ω. Answer the following questions when it is operating at full load; Question 1 What is the number of poles in this motor? 2 4 6 8 10 12 Question 2 Find the output torque in Nm.(Assume 1hp=745.7W) 1985.7 2373.6 2011.9...
A synchronous generator 480-V, 50-Hz, Y-connected, six-pole has a power rating of 50 kVA at pf...
A synchronous generator 480-V, 50-Hz, Y-connected, six-pole has a power rating of 50 kVA at pf 0.8 lagging. The synchronous Reactance Generator is 1.0 Ω per-phase. This Generator is connected to the 45 kW steam turbine. The friction loss and the core generators are respectively 1.5 kW and 1.0 kW. Question : Draw a Capability curves!
A three phase Y connected synchronous motor has negligible armature resistance and a synchronous reactance of...
A three phase Y connected synchronous motor has negligible armature resistance and a synchronous reactance of 12 ohm/phase. The motor takes 12,000kW at a line voltage of 13,200V. If the line current is adjusted so that the excitation voltage is 9000V/phase: a. What is the torque angle? b. At what power factor is the motor operating? c. What is its armature current?
A two-pole Y-connected generator rated at 13.8 kV, 20 MVA, 0.8 p.f. leading is running at...
A two-pole Y-connected generator rated at 13.8 kV, 20 MVA, 0.8 p.f. leading is running at 1800 rpm. The generator has a synchronous reac- tance of 8 Ω per phase (at 60 Hz) and a negligible armature resistance per phase. The generator is operated in parallel with an interconnected power network. Compute the following: (i) What is the torque angle of the generator at rated conditions? (ii) How many MW of power this generator can deliver?
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA at a FP = 0.8 lagging with a line voltage of 450-V. The machine stator resistance RS = 0.004 ?. The synchronous reactance is Xs=0.08 ?. The actual system load on the machine draws 900 kW at FP = 0.6 lagging. Assume that a voltage regulator has automatically adjusted the field current so that the terminal voltage is its rated value. Mechanical losses are...
A three-phase Wye-connected synchronous generator is rated 3600 rpm, 200kVA, 480V, 60 Hz. The generator’s armature...
A three-phase Wye-connected synchronous generator is rated 3600 rpm, 200kVA, 480V, 60 Hz. The generator’s armature winding resistance is RA = 0.03Ω and the synchronous reactance XS is 0.25Ω. The rotational losses are 6kW, the core losses are 4kW, and the stray losses are 1% of the output real power. The generator is delivering 200kVA power at 0.85 pf lagging at rated voltage. Taking the phase voltage at the output as a reference, answer the following questions. How many poles...
A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has...
A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has synchronous reactance of X~ = 1.0 fl . The generator is connected to a threephase delta-wye connected step-down transformer that is constructed from three individual single-phase transformers. Each the single-phase transformers has rated power of 200 kVA has a turns ratio of 4:1 where the rated primary voltage of 8.0 kV and a rated secondary of 2.0 kV and a per-unit series reactance of...