Question

(360) Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole -connected synchronous motor has 0.9Ω synchronous reactance....

(360) Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole -connected synchronous motor has 0.9Ω synchronous reactance. Friction; wind; core losses and armature resistance are neglected.

a) If the motor is operating under magnitude of phase current (ia) (180)

Ampere and power factor of 0.6 lagging,

1. Find the input power of motor in hp

2. Find the generated voltage, EA

3. Find the torque and the maximum inducible torque in current state.

b) If EA is increased by 18% find,

1. Magnitude of new armature current (ia),

2. New power factor of motor.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
410 Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole Triangle connected synchronous motor has 0.9Ω synchronous...
410 Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole Triangle connected synchronous motor has 0.9Ω synchronous reactance. Friction; wind; core losses and armature resistance are neglected. a) If the motor is operating under magnitude of phase current (ia) 230 Ampere and power factor of 0.6 lagging, 1. Find the input power of motor in hp (10p) 2. Find the generated voltage, EA (10p) 3. Find the torque and the maximum inducible torque in current state. (10p) b) If EA is...
The 400 V, 50 kVA, 0.8 power factor leading delta connected synchronous motor has synchronous reactance...
The 400 V, 50 kVA, 0.8 power factor leading delta connected synchronous motor has synchronous reactance of 3-ohm, resistance neglected. It is supplying a 12-kW load with initial power factor of 0.86 lagging. The windage and friction losses are 2.0 kW and the core losses are 1.5 kW. Determine (a) the motor efficiency; the line current; armature current; and excitation voltage. (b) If the flux of the motor is increased by 20 percent determine the excitation voltage; armature current; and...
a 460-V 100-hp 60-Hz 4 pole Y connected synchronous motor has a operating power factor 0.85...
a 460-V 100-hp 60-Hz 4 pole Y connected synchronous motor has a operating power factor 0.85 leading the aramature resistance is o.2 ohms and synchronous reactance is 12 ohms at full load the efficiency is 85% find the sum of mechanical loss core loss and stray loss when meachine is operating at full load
A 2300-V, 400-hp, 60-Hz, 1200rpm, Y-connected synchronous motor has a rated power factor of 0.8 leading....
A 2300-V, 400-hp, 60-Hz, 1200rpm, Y-connected synchronous motor has a rated power factor of 0.8 leading. The efficiency of the motor is 90 % at full load. The armature resistance is 0.3 Ω, and the synchronous reactance is 3.55 Ω. Answer the following questions when it is operating at full load; Question 1 What is the number of poles in this motor? 2 4 6 8 10 12 Question 2 Find the output torque in Nm.(Assume 1hp=745.7W) 1985.7 2373.6 2011.9...
A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a...
A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a synchronous reactance of 3.0 Ω. Its efficiency at full load is 89% (1 Hp=746 watt). (a) What is the line current of the generator at rated conditions? (b) What is the internal generated voltage EA of this motor at rated conditions?
A three phase Y connected synchronous motor has negligible armature resistance and a synchronous reactance of...
A three phase Y connected synchronous motor has negligible armature resistance and a synchronous reactance of 12 ohm/phase. The motor takes 12,000kW at a line voltage of 13,200V. If the line current is adjusted so that the excitation voltage is 9000V/phase: a. What is the torque angle? b. At what power factor is the motor operating? c. What is its armature current?
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance of 30W and negligible resistance. The generator is connected to an infinite bus at 6.6 KV and 60 Hz. a)Determine the excitation voltage (Ea) when the machine is delivering rated power at o.8 PF lagging. b)The field excitation current is increased by 10% without changing the power input from the prime mover. Find the stator current (Ia), the power factor and the reactive power...
Question A 208 V 10 Hp four pole 60 Hz Y connected induction motor has a...
Question A 208 V 10 Hp four pole 60 Hz Y connected induction motor has a full load slip of 5%. a)-What is the synchronous speed of this motor? b)-What is the shaft speed of this motor at full load? c)-What is the frequency of rotor current at full load? d)-What is the shaft torque of this motor at full load? e)-If the efficiency of this motor is 90% at full load what is the input power f)-If the efficiency...
Please be clear in concept and handwriting. A 20HP, three-phase, Wye-connected synchronous motor is connected to...
Please be clear in concept and handwriting. A 20HP, three-phase, Wye-connected synchronous motor is connected to a 277VAC, 60Hz power supply. At rated conditions, the motor runs at 3600 rpm and presents a 0.85 lagging power factor to the power supply. The per-phase armature reactance is 350m?. Armature resistance is negligible, as are all other sources of power loss. Considering rated conditions, a. draw a single-phase equivalent circuit showing V?, Ea and IA, with values. b. draw a phasor diagram...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance,...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance, Xs = 17.9, and is connected to an infinite bus at rated voltage. If the rotational and electrical losses are negligivle, what is Ia, Ef, delta, theta, Tdrive, Phasor diagram, and power flow diagram (label completely with numerical values for, A) the machine as a generator; the prime-throttle is opened and If is adjusted so that the machine delivers rated kVA, 0.8 pf lagging,...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT