Question

A power plant outputs power at 4000vots and 100amps. It then goes through a step-up transformer...

A power plant outputs power at 4000vots and 100amps. It then goes through a step-up transformer to 2.5x10^5volts. The resistance of the high tension lines is 30ohms. Use the fact that power input = power output on a transformer, P=IV=IV to find the secondary current, then work power through 30ohm transmission line.

a. What is the percentage power loss in the lines?

b. If there was no step-up transformer, what would be the percentage power loss?

Homework Answers

Answer #1

(a) Turn ration of the transformer -

N1 / N2 = 4000 / (2.5 x 10^5)

so, secondary current of the transformer -

I2 = I1 * (N1 / N2) = (100*4000) / (2.5 x 10^5) = 1.6 A

So, power loss P(L) = I^2 * R = 1.6^2 * 30 = 76.8 W

Total power = V*I = 4000 * 100 = 400000 W

So, percentage power loss in the line = (76.8 / 400000)*100 = 0.0192 %

(b) If there is no step-up transformer -

Power loss P(L) = I^2 * R = 100^2 * 30 = 300000 W

Percentage power loss in this case = (300000 / 400000)*100 = 75 %

Power loss is much higher in this case.

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A power plant produces an rms voltage of Vp = 12.0 x 10^3 V and an...
A power plant produces an rms voltage of Vp = 12.0 x 10^3 V and an rms current of Ip = 180 A. The rms voltage is stepped up to 300 x 10^3 V by a transformer before it is transmitted to a substation. The resistance of the transmission line is between the power plant and the substation is R = 1000Ω. a) What is the turns ration Ns/Np for this transformer? b )What is the rms current in the...
Suppose a power plant produces 811 kW of power and is to send that power for...
Suppose a power plant produces 811 kW of power and is to send that power for many miles over a copper wire with a total resistance of 12.0 Ω. If the power is sent across the copper wires at 48.0 kV rms, how much current flows through the wires? If the power is sent across the copper wires at 48.0 kV rms, what is the power dissipated due to the resistance of the wires at this current? What percent of...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is rated at 1000 kVA and has a step-down ratio of 8:1. The bank supplies a balance load having a power factor of 0.8 lag with a load current of 70 A. Assume ideal transformer, determine. The primary line and phase voltages The secondary line and phase voltages The secondary line and phase currents The apparent and active power at the load Total kVA capacity...
An ideal transformer has 100 turns on its primary coil and 200 turns on its secondary...
An ideal transformer has 100 turns on its primary coil and 200 turns on its secondary coil. If 120 V at 2.0 A is applied to the primary, (a) What voltage is present in the secondary? (b) What current is present in the secondary? (c) What is the output power? (d) Is this a step-up or step-down transformer? (e) Is the input power the same, larger or smaller than the output power?
Imagine an ideal transformer with 1.5 A of peak input current and 9.0 A of peak...
Imagine an ideal transformer with 1.5 A of peak input current and 9.0 A of peak output current. (a) Is this transformer step-up or step-down? (b) What is the required peak input voltage if the transformer is designed for 18 W of power? Show all work.
A pair of power transmission lines each have 2.95-Ω resistance and carry 650 Amp. If the...
A pair of power transmission lines each have 2.95-Ω resistance and carry 650 Amp. If the primary voltage of the 10:1 step-up transformer is 2.2 kV, calculate the input voltage of the step-down transformer at the other end. An electric power station that operates at 30 kV and uses a 10:1 step-up ideal transformer is producing 320 MW (Mega-Watt) of power that is to be sent to a big city which is located 200 km away with only 2.0% loss....
Seven) An ideal transformer has 25 turns on the input and 400 turns on the output....
Seven) An ideal transformer has 25 turns on the input and 400 turns on the output. There is an input voltage of 120V and an input current of 0.200A. a. What is the power input? b. What is the power output? c. What is the voltage output? d. What is the current output? e. Is this a “step up” transformer or a “step down” transformer?
An electric power station that operates at 25 kV and uses a 20:1 step-up ideal transformer...
An electric power station that operates at 25 kV and uses a 20:1 step-up ideal transformer is producing 310 MW (Mega-Watt) of power that is to be sent to a big city which is located 280 km away with only 2.0% loss. What is the resistance of the TWO wires that are being used?
7. An ideal transformer steps up 12.0 volts to 125 volts and the 2630-turn secondary supplies...
7. An ideal transformer steps up 12.0 volts to 125 volts and the 2630-turn secondary supplies 11.5 Amperes. a) Determine the current in the primary. b) Determine the turns ratio. c) What is the ratio of output power to input power?
1-Power Systems: Line Diagrams (a) Sketch a single line diagram for the following power system. There...
1-Power Systems: Line Diagrams (a) Sketch a single line diagram for the following power system. There are three 3-phase alternators supplying an 11 kV busbar and one 3-phase alternator supplying a 33 kV busbar. There are two parallel transmission lines fed from the 11 kV line and supplying a 33kV busbar. Each has a step-up and step-down transformer. One secondary feeders from the 33 kV bus bar feeds a further kV busbar through a stepdown transformer. This is further stepped...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT