Question

  A simple power system consists of a dc generator connected to a load center via a...

  A simple power system consists of a dc generator connected to a load center via a transmission line. The load resistance is 10 Ω. The transmission line is 50 km copper wire of 3 cm in diameter. If the voltage at the generator terminals is 400 V, compute the following:

a.   Voltage across the load

b.   Voltage drop across the line

c.   Line losses

d.   System efficiency

Homework Answers

Answer #1

The solution is given below.

Thank you.

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A balanced positive-sequence, Y-connected generator has an impedance of 0.3+j0.6 Ω/Φ, the terminal RMS voltage of...
A balanced positive-sequence, Y-connected generator has an impedance of 0.3+j0.6 Ω/Φ, the terminal RMS voltage of the source is 380V. The generator feeds a balanced, three-phase, Δ-connected load having an impedance of 27 + j42 Ω/Φ. The impedance of the line connecting the generator to the load is 0.6+j1.2 Ω/Φ. 1. Calculate the three line currents. 2. Calculate the line voltages at the terminals of the load. 3. Calculate the phase load currents. 4. Calculate the line voltage at the...
Two dc generators (A) and (B) with the following characteristics: Generator (A): rated voltage = 150...
Two dc generators (A) and (B) with the following characteristics: Generator (A): rated voltage = 150 V, rated current = 30 Amp, and armature resistance = 0.4 Ω. Generator (B): no-load voltage = 160 V, rated current = 20 Amp, and armature resistance = 0.6 Ω. are connected in parallel. Find: a) Circulating no-load current and terminal voltage. b) The load current when generator B floating. c) The maximum possible load power
100 MW of electrical power is delivered at 200 kV to a distribution center over a...
100 MW of electrical power is delivered at 200 kV to a distribution center over a transmission line which consumes 10% of the total power developed by the generating station in heat losses. a) What is the value of the voltage fed to the transmission line at the generator end? b) How much power would be delivered to the same load if the resistance of the transmission line was halved but the generator voltage was unaltered?
DC and AC power distribution schemes are illustrated in the circuits below. Both are intended to...
DC and AC power distribution schemes are illustrated in the circuits below. Both are intended to supply customers with power at voltage V. zPowerGrid Consider an AC power grid with components like the circuit on the right. A transmission line that has a line resistor RT with a resistance per unit length of 4.80 ⨯ 10−4 Ω/m is to be used to transmit 5.00 MW over 400 miles (6.44 ✕ 105 m). The output voltage of the generator VS is...
A wire consists of a steel center, 1mm in diameter, and a copper sheathing that is...
A wire consists of a steel center, 1mm in diameter, and a copper sheathing that is 2 mm in diameter (with a 1 mm inner diameter where the copper is fused to the steel). What is the resistance of a 10 meter-long piece of this wire, and how much current and how much power is dissipated in this wire if attached across the terminals of a 12-volt battery? Hint: are the copper and steel components of the wire in series...
A 200 V DC, 1,800 RPM shunt connected motor has an armature resistance of 0.4 ohm...
A 200 V DC, 1,800 RPM shunt connected motor has an armature resistance of 0.4 ohm and a brush resistance of 0.4 ohm; brush voltage drop of 6.0 V, independent of load. The resistance of the shunt field is 230 ohm. The full load rated line current is 40 A. When the motor is operated at no load the line current is 5 A and the speed is 1750 RPM. Calculate speed at rated load Calculate speed at .3 rated...
A permanent magnet DC generator is run at a constant speed of 800 rpm and provides...
A permanent magnet DC generator is run at a constant speed of 800 rpm and provides a terminal voltage of 150 V at its rated loading. Its armature resistance is Ra=0.2 Ω. When the generator is not loaded, the input power is 300W and Vt= 165V. a) Calculate the voltage regulation of the generator. b) Calculate the armature current. For the same machine given assume now that it is loaded with a load of RL= 0.35 Ω. c) Calculate the...
a)Explain the shunt excitation and compound excitation of DC generator. b)A 240V compound DC motor has...
a)Explain the shunt excitation and compound excitation of DC generator. b)A 240V compound DC motor has the armature, series field and shunt field resistances are 0.22 Ω, 0.04 Ω and 200 Ω respectively. On full load, the line current is 17.5 A and the motor runs at 1800 rpm. (short shunt) i) Draw the diagram and the power flow of the motor. ii) Find the back EMF of the motor. iii) Find the mechanical power developed. iv) Find the output...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA at a FP = 0.8 lagging with a line voltage of 450-V. The machine stator resistance RS = 0.004 ?. The synchronous reactance is Xs=0.08 ?. The actual system load on the machine draws 900 kW at FP = 0.6 lagging. Assume that a voltage regulator has automatically adjusted the field current so that the terminal voltage is its rated value. Mechanical losses are...
A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a...
A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a synchronous reactance of 3.0 Ω. Its efficiency at full load is 89% (1 Hp=746 watt). (a) What is the line current of the generator at rated conditions? (b) What is the internal generated voltage EA of this motor at rated conditions?