In the month of January, a certain dwelling requires heat in the amount of 2.4 x 106 kJ per day to maintain its temperature at 20 C. As a means of providing the required heating, a heat pump cycle is under consideration that would operate between the dwelling and a nearby pond at 10 C. The manufacturer claims that the net work input required to operate the heat pump is 1.6 x 105 kJ/day. Evaluate this claim.
Here, the high temperature heat reservoir (or the hot reservoir) is the dwelling and the low temperature heat reservoir(or the cold reservoir) is the pond. A heat pump operates between the hot and cold reservoir.
Given: Temperature of the dwelling, TH=200C=293.15 K
Temperature of the pond, TL= 100C= 283.15 K
Work required by the heat pump, Wnet= 1.6*105 kJ/day
Heat supplied to the high temperature reservoir, QH= 2.4*106 kJ/day
Evaluation of the claim is done by determining the Coefficient of Performance (COP) of a Carnot heat pump and the Actual COP.
The actual COP of a heat pump, COPactual is calculated as
COP of a Carnot heat pump, COPCarnot is calculated using the expression
where TH and TL is the Temperature of hot and cold reservoir respectively
As COPactual < COPCarnot , the claim made is possible.