The design data for an air-conditioning plant of a restaurant is given below
Outdoor design conditions = 35ºC DBT and 24ºC WBT
Indoor design conditions = 27ºC DBT and 55% RH
Seating capacity of the restaurant = 50
Latent heat gain per person = 44 W
Latent heat gain from meals per person = 6 W
Sensible heat gain per person =58 W
Sensible heat gain from meals per person = 3.5 W
Number of service employees = 5
Latent heat gain per employee = 75 W
Sensible heat gain per employee = 58 W
Sensible heat gain from outside = 8.14 kW
Sensible heat gain from inside equipment = 2.9 kW
Latent heat gain from inside equipment = 0.7 kW
Rate of infiltrated air = 400 m3 / h
Rate of fresh air supply = 1600 m3 / h
Minimum temperature of air supplied to room = 17ºC DBT
The fan is situated before the conditioner and has a motor of 11 kW. Calculate (a) volume of air passing
through the room in m3 / h (b) percentage of recirculated air; (c) apparatus dew point temperature and by-pass
Please refer the following images for the solution.