Question

A 300MVA, 20KV three-phase generator has a sub-transient reactance of 20%. The generator supplies two parallel...

A 300MVA, 20KV three-phase generator has a sub-transient reactance of 20%. The generator supplies two parallel synchronous motors (M1 and M2) over a 100km transmission line. The line has two transformers T1 and T2 at the beginning and at the end of the line respectively. Both motors are rated at 13.0KV with X"=20%. Motor M1 has a rated input of 100MVA and M2 has a rated input of 50MVA. The transformer T1 is rated 350MVA, 20/230KV and T2 is rated 100MVA, 220/13.2KV. Both transformers have a leakage reactance of 10%. The series reactance of the transmission line is 0.1ohms/Km.

a)Draw the reactance diagram of the circuit with all reactances marked in per unit. Select the generator rating as base.

b) If the motors M1, and M2 from above have inputs of 100MW and 80MW respectively at 13.0KV, and both operate at unity power factor. Find the voltage at the terminal of the generator.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is connected to a three phase Y-Y transformer T1 which feeds a 132 kV 10 miles transmission line having an impedance per phase of 2 + j5 ?/mile. At the receiving end of the transmission line is a Y-Y step down transformer T2. Three loads are connected to the secondary side of the transformer T2. Loads are as follows: Load#1 40 MVA at 0.8 pf...
A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has...
A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has synchronous reactance of X~ = 1.0 fl . The generator is connected to a threephase delta-wye connected step-down transformer that is constructed from three individual single-phase transformers. Each the single-phase transformers has rated power of 200 kVA has a turns ratio of 4:1 where the rated primary voltage of 8.0 kV and a rated secondary of 2.0 kV and a per-unit series reactance of...
A synchronous generator and motor are rated 30,000kVA, 13.2kV, and both have subtransient reactances of 20%....
A synchronous generator and motor are rated 30,000kVA, 13.2kV, and both have subtransient reactances of 20%. The line connecting them has a reactance of 10% on the base of the machine ratings. The motor is drawing 20,000kW at 0.8 power-factor leading and a terminal voltage of 12.8kV when a symmetrical three phase fault occurs at the generator terminals. Find A synchronous generator and motor are rated 30,000kVA, 13.2kV, and both have subtransient reactances of 20%. The line connecting them has...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of 1.33 p.u. The generator achieves rated open circuit voltage at a field current of 325 A. The generator is connected to a network with an equivalent line-line voltage of 11 kV and an equivalent impedance of 0.17 pu on the generator base. The generator is loaded to a real power of 110 MW. a- Find the generated voltage Eaf in p.u. such that the...
•The 3-phase system consists of a generator, circuit breaker, power transformer and extra high voltage transmission...
•The 3-phase system consists of a generator, circuit breaker, power transformer and extra high voltage transmission line. •The generator is rated at 60Hz, 1559Mva and 24kV. The sub-transient reactance is 2*%. The winding connection is wye with the neutral grounded. •The transformer is a 1550Mva, 3-phase, shell type, 2-winding transformer with a 24kV delta winding and a 525kV grounded wye winding. Neglect saturation and core losses. The exciting current is 1.0% of the rated current. The capacitance of each low...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance,...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance, Xs = 17.9, and is connected to an infinite bus at rated voltage. If the rotational and electrical losses are negligivle, what is Ia, Ef, delta, theta, Tdrive, Phasor diagram, and power flow diagram (label completely with numerical values for, A) the machine as a generator; the prime-throttle is opened and If is adjusted so that the machine delivers rated kVA, 0.8 pf lagging,...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load at the low voltage side. The load absorbs 5 MVA, 0.7 power factor lagging at line to line voltage 0.9 kV. The transformer has an equivalent reactance 0.05 Ω/phase. Assuming 10 MVA and 1 kV as base value, draw the per unit diagram for the system. Find the Line to Line voltage at the primary side of the transformer. b) A three-phase synchronous generator...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance of 30W and negligible resistance. The generator is connected to an infinite bus at 6.6 KV and 60 Hz. a)Determine the excitation voltage (Ea) when the machine is delivering rated power at o.8 PF lagging. b)The field excitation current is increased by 10% without changing the power input from the prime mover. Find the stator current (Ia), the power factor and the reactive power...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance of 6.08 Ohms as referred to its high-voltage terminals. The transformer is supplying a load of 375 MVA, with 0.89 power factor lagging at a voltage of 24 kV (line-to-line) on its low-voltage side. It is supplied from a feeder whose impedance is 0.17 + j 2.2 Ohms connected to its high-voltage terminals. The total load in the system remains constant at 375 MVA....
Please be clear in conceot and handwriting, thank you. A 20 kVA three-phase synchronous machine is...
Please be clear in conceot and handwriting, thank you. A 20 kVA three-phase synchronous machine is connected to a 480 V, 60 Hz electrical service. The per-phase armature reactance is 80%. Armature resistance is negligible, as are all other sources of power loss. Part A: Motor Configuration The machine is configured to run as a motor. Its rated mechanical power is 20 HP and it is 94% efficient. The motor provides rated output mechanical power. The excitation is set such...