Question

2. Three phase loads are in Y connection. Each load has a 20 Ω resistor and...

2. Three phase loads are in Y connection. Each load has a 20 Ω resistor and a 12 Ω reactor series. If the line voltage is 440 V, calculate the following:


a. The total active power, reactive power, and apparent power supplied to the three-phase load.


b. The voltage across each resistor.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is connected to a three phase Y-Y transformer T1 which feeds a 132 kV 10 miles transmission line having an impedance per phase of 2 + j5 ?/mile. At the receiving end of the transmission line is a Y-Y step down transformer T2. Three loads are connected to the secondary side of the transformer T2. Loads are as follows: Load#1 40 MVA at 0.8 pf...
Chapter 20, Problem 062 A 84.0-Ω resistor is connected in parallel with a 179.6-Ω resistor. This...
Chapter 20, Problem 062 A 84.0-Ω resistor is connected in parallel with a 179.6-Ω resistor. This parallel group is connected in series with a 25.3-Ω resistor. The total combination is connected across a 21.2-V battery. Find (a) the current and (b) the power dissipated in the 179.6-Ω resistor. (a) Number _____ Units _____ (b) Number ________ Units ______
Three star-connected coils are drawing line current of 30A from a three phase supply. Also, total...
Three star-connected coils are drawing line current of 30A from a three phase supply. Also, total apparent and active powers of 25kVA and 11 kW respectively are absorbed by the coils. By assuming that the each coil is characterized by equal impedance, determine: i. the line and phase voltages ii. the total reactive power (1 mark) iii. the impedance of each coil. c) If the coils in Q2(b) are suddenly reconfigured into delta connection, calculate the new line currents and...
The no-load (line) voltage of a 6-pole, 72-slot, 1200-rpm, three-phase, Y-connected, synchronous generator is 1732 V....
The no-load (line) voltage of a 6-pole, 72-slot, 1200-rpm, three-phase, Y-connected, synchronous generator is 1732 V. There are 10 conductors per slot. For a series connection, determine (a) the frequency of the induced emf and (b) the flux per pole.
Three resistors having resistances of R1 = 1.52 Ω , R2 = 2.32 Ω and R3...
Three resistors having resistances of R1 = 1.52 Ω , R2 = 2.32 Ω and R3 = 4.94 Ω respectively, are connected in series to a 28.4 V battery that has negligible internal resistance. Find the equivalent resistance of the combination. Find the current in each resistor. Find the total current through the battery. Find the voltage across each resistor. Find the power dissipated in each resistor. Which resistor dissipates the most power, the one with the greatest resistance or...
A balanced ?-connected load has an impedance of 60+ j45 ? per phase. The load is...
A balanced ?-connected load has an impedance of 60+ j45 ? per phase. The load is fed through a line having an impedance of 0.8+ j0.6 ? per line. The phase voltage at the terminals of the load is ???????? = 480 ?? . The sequence is positive. Use AB v as the reference at the load. The source is required to be calculated for either Wye or Delta connection. a) Draw the 3-phase system b) Draw the a-phase equivalent...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load at the low voltage side. The load absorbs 5 MVA, 0.7 power factor lagging at line to line voltage 0.9 kV. The transformer has an equivalent reactance 0.05 Ω/phase. Assuming 10 MVA and 1 kV as base value, draw the per unit diagram for the system. Find the Line to Line voltage at the primary side of the transformer. b) A three-phase synchronous generator...
The magnitude of the phase voltage of an ideal balanced three-phase Y-connected source is 110 V...
The magnitude of the phase voltage of an ideal balanced three-phase Y-connected source is 110 V . The source is connected to a balanced Y-connected load by a distribution line that has an impedance of 0.1+0.8i Ω/ϕ . The load impedance is 20.2+14.8i Ω/ϕ . The phase sequence of the source is acb. Use the a-phase voltage of the source as the reference. Part A: Specify the magnitude and phase angle of the line current IaA. Part B: Specify the...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging •...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance of 6.08 Ohms as referred to its high-voltage terminals. The transformer is supplying a load of 375 MVA, with 0.89 power factor lagging at a voltage of 24 kV (line-to-line) on its low-voltage side. It is supplied from a feeder whose impedance is 0.17 + j 2.2 Ohms connected to its high-voltage terminals. The total load in the system remains constant at 375 MVA....