Question:A 2-wire d.c. distributor AB is fed at both ends at the same
voltage of 230...
Question
A 2-wire d.c. distributor AB is fed at both ends at the same
voltage of 230...
A 2-wire d.c. distributor AB is fed at both ends at the same
voltage of 230 V. The length of the distributor is 500 meters and
the loads are tapped off from the end A as shown below:
Load: 100 A 60 A 40 A 100 A
Distance: 50 m 150 m 250 m 400 m
If the maximum voltage drop of 5.5 V is to be allowed, find
the X-sectional area of each conductor and point of minimum
potential. Specific resistance of conductor material may be taken
as 1.73x10^-8 Ohm m.