Question

Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...

Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging

• a) Draw an equivalent circuit of the system indicating all impedances in per unit. Choose 10 MVA, 13.2 kV as the base values of load.

• b) Calculate the per unit source voltage that must be supplied to the high voltage side of transformer to supply the load ar rated voltage.

• c) Find the per unit current based on the high voltage side of the transformer.

Homework Answers

Answer #1

For a transformer we have -

Given base values as 10 MVA and 13.2 KV

For a transfromer PU

Base current = Base KV/ Base V

IB = 10M/ 1.732 *13.2 K = 437.386 A

Base impedance -

ZB = KVB 2 /MVAB = 17.424 ohms

per unit system equivalent circuit -

Also ZPU will be same on either side of transformer ie, primary and secondary

Given Z = 0.007 + j0.075 then

Now Zpu old = Zact / ZB

=  0.007 + j0.075 / 17.424

= 0.4 + j 4.3 m ohms

now

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load at the low voltage side. The load absorbs 5 MVA, 0.7 power factor lagging at line to line voltage 0.9 kV. The transformer has an equivalent reactance 0.05 Ω/phase. Assuming 10 MVA and 1 kV as base value, draw the per unit diagram for the system. Find the Line to Line voltage at the primary side of the transformer. b) A three-phase synchronous generator...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is connected to a three phase Y-Y transformer T1 which feeds a 132 kV 10 miles transmission line having an impedance per phase of 2 + j5 ?/mile. At the receiving end of the transmission line is a Y-Y step down transformer T2. Three loads are connected to the secondary side of the transformer T2. Loads are as follows: Load#1 40 MVA at 0.8 pf...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance of 6.08 Ohms as referred to its high-voltage terminals. The transformer is supplying a load of 375 MVA, with 0.89 power factor lagging at a voltage of 24 kV (line-to-line) on its low-voltage side. It is supplied from a feeder whose impedance is 0.17 + j 2.2 Ohms connected to its high-voltage terminals. The total load in the system remains constant at 375 MVA....
A three-phase transformer has a nameplate rating of 20 MVA, and the voltage rating of 345kV...
A three-phase transformer has a nameplate rating of 20 MVA, and the voltage rating of 345kV wye /34.5kV delta with a leakage reactance of 12% and transformer connection is wye-delta. Select a base of 20 MVA and 345 kV on the high-voltage side. Please determine the following: (a) Turn ratio of windings (b) Transformer reactance referred to low-voltage side in ohms (c) Transformer reactance referred to low-voltage side in per units
1- 30-kV, three-phase transmission line has a per phase series impedance of z = 0.05+j0.45 ohm...
1- 30-kV, three-phase transmission line has a per phase series impedance of z = 0.05+j0.45 ohm per Km and a per phase shunt admittance of y = j3.4x10-6 siemens per km. The line is 80 km long. Using the nominal π model, determine a The transmission line ABCD constants. b Find the sending end voltage and current, voltage regulation, the sending end power and the transmission efficiency when the line delivers 1. 200 MVA, 0.8 lagging power factor at 220...
1- A 69-kV, three-phase short transmission line is 16 km long. The line has a per...
1- A 69-kV, three-phase short transmission line is 16 km long. The line has a per phase series impedance of 0.125 + j0.4375 ohm per km. Determine the sending end voltage, voltage regulation, the sending end power, and the transmission efficiency when the line delivers a. 70 MVA, 0.8 lagging power factor at 64 kV b. 120 MW, unity power factor at 64 kV 2-three-phase, completely transposed 345-kV, 200 km line has two 795,000- cmil 26/2 ACSR conductor per bundle...
A feeder having an impedance of 1.0+j3.2ohms is connected to the primary side of a step-down...
A feeder having an impedance of 1.0+j3.2ohms is connected to the primary side of a step-down three phase transformer rated at 132:22KV, 200MVA and that has a series reactance of 0.14pu. The transformer supplies a load of 190MVA with a 0.90 lagging power factor at rated voltage. a) Caculate the per unit impedance of the feeder and the per unit load current. Use the transformer ratings as base values. b) Calculate the voltage at the sending end of the feeder...
A 3? power system consists of a Y-connected source (300 MVA, 23 kV) supplying a Y-connected...
A 3? power system consists of a Y-connected source (300 MVA, 23 kV) supplying a Y-connected load (240 MVA, 230 kV, PF = 0.90 lagging) through a step-up transformer (330 MVA, 23?/230Y kV, X = 0.11 per unit). Take into account the transformer’s phase shift and choose the load terminal voltage VAN as the reference. Use base values of 100 MVA and 230 kV at the load. (a) Find the per-unit load currents (IA, IB, and IC). (b) Find the...
QUESTION A 60-Hz turbogeneralor is rated 500 MVA, 22 kV . It is Y-connected and solidly...
QUESTION A 60-Hz turbogeneralor is rated 500 MVA, 22 kV . It is Y-connected and solidly grounded and is operating at rated voltage at no load. It is disconnected from the ,rest of the system. Its reactances are Xd'' = X1 = X2 = 0.15 and Xo = 0.05 per unit. Find the ratio of the sub transient line current for a single line-to-ground fault to the sub transient line current for a symmetrical three-phase fault.
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of 1.33 p.u. The generator achieves rated open circuit voltage at a field current of 325 A. The generator is connected to a network with an equivalent line-line voltage of 11 kV and an equivalent impedance of 0.17 pu on the generator base. The generator is loaded to a real power of 110 MW. a- Find the generated voltage Eaf in p.u. such that the...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT