Question

For a section of a substation and a switchboard with a 500 kW motor feeder and...

For a section of a substation and a switchboard with a 500 kW motor feeder and a 1500 kVA transformer feeder at 6.6 kV operating voltage calculate:

  • The current of the transformer feeder.
  • The current of the motor feeder.

Assume power factor as 0.85 and motor efficiency as 90%.

Show all calculations.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
The 400 V, 50 kVA, 0.8 power factor leading delta connected synchronous motor has synchronous reactance...
The 400 V, 50 kVA, 0.8 power factor leading delta connected synchronous motor has synchronous reactance of 3-ohm, resistance neglected. It is supplying a 12-kW load with initial power factor of 0.86 lagging. The windage and friction losses are 2.0 kW and the core losses are 1.5 kW. Determine (a) the motor efficiency; the line current; armature current; and excitation voltage. (b) If the flux of the motor is increased by 20 percent determine the excitation voltage; armature current; and...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V,...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V, 50 Hz, io = 1.2%; ukN = 6%, idle losses 2450 W, rated copper losses of power 14500 W; Dy5. a) Calculate primary and secondary line and phase currents. b) Secondary at 75% load in power factor with 0.85 inductance and 0.85 capacity calculate the voltage separately. Compare and interpret the results. capacity at what time of day can the upload be seen? To...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V,...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V, 50 Hz, io = 1.2%; ukN = 6%, idle losses 2450 W, rated copper losses of power 14500 W; Dy5. a) Calculate primary and secondary line and phase currents. b) Secondary at 75% load in power factor with 0.85 inductance and 0.85 capacity calculate the voltage separately. Compare and interpret the results. capacity at what time of day can the upload be seen? To...
A 100 KW (OUT PUT), 3300V, 50 Hz, 3-Phase star connected induction motor has a synchronous...
A 100 KW (OUT PUT), 3300V, 50 Hz, 3-Phase star connected induction motor has a synchronous speed of 500 rpm. The full load slip is 1.8%and full load power factor 0.85. Stator copper loss=2440W. Iron loss=3500W. Rotational losses= 1200W. calculate : The rotor copper loss The line current The full load motor efficiency.
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging •...
A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has...
A three-phase wye-connected (Y) synchronous generator is operating at Ea = 8.OLO° kV (lineneutral) and has synchronous reactance of X~ = 1.0 fl . The generator is connected to a threephase delta-wye connected step-down transformer that is constructed from three individual single-phase transformers. Each the single-phase transformers has rated power of 200 kVA has a turns ratio of 4:1 where the rated primary voltage of 8.0 kV and a rated secondary of 2.0 kV and a per-unit series reactance of...
A 5-kW, 220-V shunt motor has an armature resistance of 0.15 ? and a field-circuit resistance...
A 5-kW, 220-V shunt motor has an armature resistance of 0.15 ? and a field-circuit resistance of 100 ?. The motor delivers rated output power at rated voltage when its armature current is 20 A. When the motor is operating at rated voltage, the speed is observed to be 1000 r/min when the machine is loaded such that the armature current is 15 A. In order to protect both the motor and the dc supply under starting conditions, an external...
A separate excited DC motor is running at 1000 rpm when the armature voltage is 600...
A separate excited DC motor is running at 1000 rpm when the armature voltage is 600 V. The motor has a field constant Kphi = 4 V.sec and the armature resistance of the motor is 0.8 Ohms. i. Calculate the value of the resistance of the dynamic braking at full load. The armature current should be limited to 200 % of the rated value. ii. If the motor operates in regenerative braking at a speed of 1200 rpm, calculate the...
Please be clear in conceot and handwriting, thank you. A 20 kVA three-phase synchronous machine is...
Please be clear in conceot and handwriting, thank you. A 20 kVA three-phase synchronous machine is connected to a 480 V, 60 Hz electrical service. The per-phase armature reactance is 80%. Armature resistance is negligible, as are all other sources of power loss. Part A: Motor Configuration The machine is configured to run as a motor. Its rated mechanical power is 20 HP and it is 94% efficient. The motor provides rated output mechanical power. The excitation is set such...
ACCT 630, Advanced Corporate Taxation , ACCT630-01 PROJECT – S CORPORATIONS (1) Your assignment is to...
ACCT 630, Advanced Corporate Taxation , ACCT630-01 PROJECT – S CORPORATIONS (1) Your assignment is to calculate the answers for Problem 5A(9) of the Study Problems as set forth below. (3) Check figures: (a) Addition to each shareholder’s stock basis 67 (b) Addition to each shareholder’s AAA 17 (4) Problem The stock of X is owned equally by two shareholders: Y (an individual with a stock basis of $100) and A (an individual with a stock basis of $40). X...