Question

A 525 V to 110 V, 50 Hz, single phase transformer has a no-load current on...

A 525 V to 110 V, 50 Hz, single phase transformer has a no-load current on the HV side, of 0,5 A at a power factor of 0.36 lagging. Answer the following questions regarding this transformer: 3.1 If a load current of 24 A flows on the LV side, at a power factor of 0.8 lagging, find the value of the primary current and the power factor.   State the assumption and sketch the phasor diagram representing this situation.    (10) 3.2 Determine the values of Rcore and Xmag and sketch this part of the transformer’s equivalent circuit and label it with the variables.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A 10-kVA, 250 / 100-V, 50-Hz single-phase transformer gave the following open and short circuit test...
A 10-kVA, 250 / 100-V, 50-Hz single-phase transformer gave the following open and short circuit test results: Open circuit test: 250 V, 2.6 A, power factor: 0.3 on HV side. Short circuit test: 18 V, 80 A, input power: 240 W on HV side. Calculate the following: 4.1 The equivalent circuit parameters of the transformer. (6) 4.2 The efficiency at full load unity power factor. (NB the test current is not at full load) (6) 4.3 The load at which...
Determine the transformer equivalent circuit components referred to the LV side and sketch the equivalent circuit....
Determine the transformer equivalent circuit components referred to the LV side and sketch the equivalent circuit. Calculate the transformer voltage regulation at full load with load power factor of 0.9 lagging. Below is the test result which can be used to determine the value of the components for the equivalent circuit. Power of the transformer = 1 kVA Open circuit test: LV winding Voltage = 110 V LV side ammeter = 690 mA LV side wattmeter = 18 W HV...
A 2.2 KVA, 440---220 V, 60 Hz, step-down transformer has the following parameters: Rp= 3.0 Ω,...
A 2.2 KVA, 440---220 V, 60 Hz, step-down transformer has the following parameters: Rp= 3.0 Ω, Xp= 4.0 Ω, Rs= 2.5 Ω, Xs= 2.0 Ω, Rc= 60 KΩ, and Xm = 15 KΩ. The transformer is operating at full load with a power factor of 0.707 lagging. The magnetizing branch impedance can be ignored. a) Draw the transformer’s equivalent T-circuit, b) Find the equivalent winding impedance referred to the high side, c) Calculate the primary and secondary currents, d) Determine...
A single-phase transformer has 2400 turns on the primary and 600 turns on the secondary. Its...
A single-phase transformer has 2400 turns on the primary and 600 turns on the secondary. Its no-load current is 4A at a power factor of 0.25 lagging. Assuming the volt drop in the windings is negligible, calculate the primary current and power factor when the secondary current is 80A at a power factor of 0.8 lagging.
1. A single phase circuit has a load of 500kVa at a power factor of 0.707...
1. A single phase circuit has a load of 500kVa at a power factor of 0.707 lagging. Calculate the kVA of the capacitors needed to improve the power factor to unity 3. When connected to a 120-v(rms), 60Hz power line, a load absorbes 4 kw at a lagging power factor of 0.8. Find the capacitance necessary to raise the pf to 0.9 4. A three phase motor draws 20kva at 0.707 power factor lagging from a 208V source. Determine the...
A 20 kVA single phase transformer 4800/480V has primary resistance and reactance of 5Ω and 15Ω...
A 20 kVA single phase transformer 4800/480V has primary resistance and reactance of 5Ω and 15Ω respectively, while the resistance and reactance of secondary winding is 0.1Ω and 0.15 Ω respectively. Calculate: (i) The parameter referred to primary side of transformer and draw the equivalent circuit (ii) The approximate value of secondary voltage at full load power factor of 0.8 lagging if 4.8kV primary supply
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging •...
Example: The load with lagging 0.8 PF absorbs 60 watts of a 100 V, 60 Hz...
Example: The load with lagging 0.8 PF absorbs 60 watts of a 100 V, 60 Hz power line. Required to correct power factor to 0.9 lag. Find: 3- The original and last line current b) The value of the element to be added to achieve the required pf correction ... power factor
A 50-Hz, two-pole, 825 kVA, 2300 V, three-phase synchronous machine has a synchronous reactance of 7.47...
A 50-Hz, two-pole, 825 kVA, 2300 V, three-phase synchronous machine has a synchronous reactance of 7.47 and achieves rated open-circuit terminal voltage at a field current of 147 A. c. For a constant load power of 700 kW, write a MATLAB script to plot the terminal current as a function of field current. For your plot, let the field current vary between a minimum value corresponding to a machine loading of 825 kVA, leading power factor, and a maximum value...
A 400-k VA, 2300 230, 60-hz transformer supplies a 0.8 lagging power-factor load whose KVA Is...
A 400-k VA, 2300 230, 60-hz transformer supplies a 0.8 lagging power-factor load whose KVA Is adjustable from no load to 120 percent rated KVA. The percent resistance, percent reactance, and percent core loss are 56, 3.16, and 0.42 respectively. For 2 KVA increments of load, tabulate and plot the efficiency of the transformer from no load to 120 percent rated load. Please state the formulas clearly
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT