Question

A delta connected balanced load with impedance "20 - j15" is connected to a star connected...

A delta connected balanced load with impedance "20 - j15" is connected to a star connected generator in positive sequence with Van = "107.43 - j312". Calculate phase and line currents and voltages, also draw the configuration described with the voltage and current labels.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A balanced ?-connected load has an impedance of 60+ j45 ? per phase. The load is...
A balanced ?-connected load has an impedance of 60+ j45 ? per phase. The load is fed through a line having an impedance of 0.8+ j0.6 ? per line. The phase voltage at the terminals of the load is ???????? = 480 ?? . The sequence is positive. Use AB v as the reference at the load. The source is required to be calculated for either Wye or Delta connection. a) Draw the 3-phase system b) Draw the a-phase equivalent...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is rated at 1000 kVA and has a step-down ratio of 8:1. The bank supplies a balance load having a power factor of 0.8 lag with a load current of 70 A. Assume ideal transformer, determine. The primary line and phase voltages The secondary line and phase voltages The secondary line and phase currents The apparent and active power at the load Total kVA capacity...
calculate the line and neutral currents for the following unbalanced wye-connected impedances: Zan = 2 +...
calculate the line and neutral currents for the following unbalanced wye-connected impedances: Zan = 2 + j5 Ω Zbn = 8 + j0 Ω Zcn = 1 - j15 Ω the voltage source is a balanced three-phase system, 208 V line to line. Assume an abc phase sequence and use Van as the reference phasor.
A balanced wye-connected three-phase source has line-to-neutral voltages of 400 V rms. - Find the rms...
A balanced wye-connected three-phase source has line-to-neutral voltages of 400 V rms. - Find the rms line-to-line voltage magnitude. - If this source is applied to a wye-connected load composed of three 33 Ω resistances, find the rms line-current magnitude. - If this source is applied to a wye-connected load composed of three 33 Ω resistances, find the total power delivered.
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is connected to a three phase Y-Y transformer T1 which feeds a 132 kV 10 miles transmission line having an impedance per phase of 2 + j5 ?/mile. At the receiving end of the transmission line is a Y-Y step down transformer T2. Three loads are connected to the secondary side of the transformer T2. Loads are as follows: Load#1 40 MVA at 0.8 pf...
A feeder having an impedance of 1.0+j3.2ohms is connected to the primary side of a step-down...
A feeder having an impedance of 1.0+j3.2ohms is connected to the primary side of a step-down three phase transformer rated at 132:22KV, 200MVA and that has a series reactance of 0.14pu. The transformer supplies a load of 190MVA with a 0.90 lagging power factor at rated voltage. a) Caculate the per unit impedance of the feeder and the per unit load current. Use the transformer ratings as base values. b) Calculate the voltage at the sending end of the feeder...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging •...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA at a FP = 0.8 lagging with a line voltage of 450-V. The machine stator resistance RS = 0.004 ?. The synchronous reactance is Xs=0.08 ?. The actual system load on the machine draws 900 kW at FP = 0.6 lagging. Assume that a voltage regulator has automatically adjusted the field current so that the terminal voltage is its rated value. Mechanical losses are...
•The 3-phase system consists of a generator, circuit breaker, power transformer and extra high voltage transmission...
•The 3-phase system consists of a generator, circuit breaker, power transformer and extra high voltage transmission line. •The generator is rated at 60Hz, 1559Mva and 24kV. The sub-transient reactance is 2*%. The winding connection is wye with the neutral grounded. •The transformer is a 1550Mva, 3-phase, shell type, 2-winding transformer with a 24kV delta winding and a 525kV grounded wye winding. Neglect saturation and core losses. The exciting current is 1.0% of the rated current. The capacitance of each low...
A 100 KW (OUT PUT), 3300V, 50 Hz, 3-Phase star connected induction motor has a synchronous...
A 100 KW (OUT PUT), 3300V, 50 Hz, 3-Phase star connected induction motor has a synchronous speed of 500 rpm. The full load slip is 1.8%and full load power factor 0.85. Stator copper loss=2440W. Iron loss=3500W. Rotational losses= 1200W. calculate : The rotor copper loss The line current The full load motor efficiency.
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT