Question

A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of...

A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of 1.33 p.u. The generator achieves rated open circuit voltage at a field current of 325 A. The generator is connected to a network with an equivalent line-line voltage of 11 kV and an equivalent impedance of 0.17 pu on the generator base. The generator is loaded to a real power of 110 MW.

a- Find the generated voltage Eaf in p.u. such that the network is operating at unity power factor at the external network equivalent voltage. Find the corresponding field current, the generator terminal voltage and power factor.

b- Assume that the generator is operating at its rated terminal voltage. Find the generated voltage Eaf in p.u., the corresponding field current, the generator terminal current and power factor.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load at the low voltage side. The load absorbs 5 MVA, 0.7 power factor lagging at line to line voltage 0.9 kV. The transformer has an equivalent reactance 0.05 Ω/phase. Assuming 10 MVA and 1 kV as base value, draw the per unit diagram for the system. Find the Line to Line voltage at the primary side of the transformer. b) A three-phase synchronous generator...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance of 30W and negligible resistance. The generator is connected to an infinite bus at 6.6 KV and 60 Hz. a)Determine the excitation voltage (Ea) when the machine is delivering rated power at o.8 PF lagging. b)The field excitation current is increased by 10% without changing the power input from the prime mover. Find the stator current (Ia), the power factor and the reactive power...
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms...
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms per phase. The machine is connected to kV, 60 Hz bus and is operated as synchronous condenser (synchronous motor at no-load condition) a. For normal excitation (excitation voltage terminal voltage), find the line current. Draw the phasor diagram b. If the excitation is increased to 150% of the normal excitation, find the line current and reactive power delivered or absorbed by the bus. Draw...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is...
A 100 MVA, 13.2 kV three phase generator (G) having a synchronous reactance of 10% is connected to a three phase Y-Y transformer T1 which feeds a 132 kV 10 miles transmission line having an impedance per phase of 2 + j5 ?/mile. At the receiving end of the transmission line is a Y-Y step down transformer T2. Three loads are connected to the secondary side of the transformer T2. Loads are as follows: Load#1 40 MVA at 0.8 pf...
A 50-Hz, two-pole, 825 kVA, 2300 V, three-phase synchronous machine has a synchronous reactance of 7.47...
A 50-Hz, two-pole, 825 kVA, 2300 V, three-phase synchronous machine has a synchronous reactance of 7.47 and achieves rated open-circuit terminal voltage at a field current of 147 A. c. For a constant load power of 700 kW, write a MATLAB script to plot the terminal current as a function of field current. For your plot, let the field current vary between a minimum value corresponding to a machine loading of 825 kVA, leading power factor, and a maximum value...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance of 6.08 Ohms as referred to its high-voltage terminals. The transformer is supplying a load of 375 MVA, with 0.89 power factor lagging at a voltage of 24 kV (line-to-line) on its low-voltage side. It is supplied from a feeder whose impedance is 0.17 + j 2.2 Ohms connected to its high-voltage terminals. The total load in the system remains constant at 375 MVA....
A three phases, 6 MVA, 22 kV, 60 Hz synchronous machine has a synchronous reactance of...
A three phases, 6 MVA, 22 kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms per phase and has negligible stator resistance. The machine is connected to the 22 kV, 60 Hz bus and is operated as a synchronous condenser, Neglect rotational losses 7 a) For normal excitation, find the stator current. Draw the phasor diagram. b) If the excitation is increased to 120 percent of the normal excitation, find the stator current and power factor, draw...
A 3 phase 11 kv,25 mva, 60 Hz salient pole synchronous motor is running from a...
A 3 phase 11 kv,25 mva, 60 Hz salient pole synchronous motor is running from a 11 Kv, 60 Hz balanced three phase supply the meachince reactances are Xd=1.2 pu and Xq=0.6 pu ,neglect the meachanicalloss and armature copper loss the maximum power input is obtained with no field excitation determine the power factor of motor
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance,...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance, Xs = 17.9, and is connected to an infinite bus at rated voltage. If the rotational and electrical losses are negligivle, what is Ia, Ef, delta, theta, Tdrive, Phasor diagram, and power flow diagram (label completely with numerical values for, A) the machine as a generator; the prime-throttle is opened and If is adjusted so that the machine delivers rated kVA, 0.8 pf lagging,...
The test results of a three-phase synchronous generator with the rated voltage of 6,600V and the...
The test results of a three-phase synchronous generator with the rated voltage of 6,600V and the capacity of 50 MVA are as follows. No-load test result: When the terminal voltage was 6,600V, the field current was 1280A. Short circuit test result: The field current required to flow the rated current was 1600A. Find the rated current of this generator Find the short-circuit ratio. However, the second decimal shall be rounded off to obtain the first decimal Find the synchronous reactance....
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT