Question

Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V,...

Plate values ​​of a three-phase transformer are given below:
1600 kVA, 15 kV / 400 V, 50 Hz, io = 1.2%; ukN = 6%, idle losses 2450 W, rated
copper losses of power 14500 W; Dy5.
a) Calculate primary and secondary line and phase currents.
b) Secondary at 75% load in power factor with 0.85 inductance and 0.85 capacity
calculate the voltage separately. Compare and interpret the results. capacity
at what time of day can the upload be seen? To prevent voltage change
What solution should be applied?
c) Calculate the rated operating efficiency and maximum efficiency of the transformer.
d) Draw the fastening group. How is this transformer parallel with the transformer Dy11 connected
run?
e) If this transformer is operated at 60 Hz, which sizes change how?
Your review.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V,...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V, 50 Hz, io = 1.2%; ukN = 6%, idle losses 2450 W, rated copper losses of power 14500 W; Dy5. a) Calculate primary and secondary line and phase currents. b) Secondary at 75% load in power factor with 0.85 inductance and 0.85 capacity calculate the voltage separately. Compare and interpret the results. capacity at what time of day can the upload be seen? To...
Plate values of a three-phase transformer are given below: 1600 kVA, 15 kV / 0,4 kV,...
Plate values of a three-phase transformer are given below: 1600 kVA, 15 kV / 0,4 kV, 50 Hz, i0 = 1.2%; ukN= 6%, idle losses 2450 W, rated power copper losses 14500 W; Dy5 connected.. III) There is 75% load in the power factor with 0.85 inductance and 0.85 capacity. At what times of the day can capacity loading be seen? What solution should be applied to prevent voltage change? IV) Draw the fastening group. How can this transformer be...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is rated at 1000 kVA and has a step-down ratio of 8:1. The bank supplies a balance load having a power factor of 0.8 lag with a load current of 70 A. Assume ideal transformer, determine. The primary line and phase voltages The secondary line and phase voltages The secondary line and phase currents The apparent and active power at the load Total kVA capacity...
A single phase transformer rated at 3000 KVA, 69kV, 60 Hz has a total internal impedance...
A single phase transformer rated at 3000 KVA, 69kV, 60 Hz has a total internal impedance Zp of 127ohm, referred to the primary side. Calculate: a) primary and secondary currents b) voltage regulation from no load to full load for 2000 kW resistive load, knowing that the primary voltage supply is fixed at 69 kV. c) primary and secondary currents if the secondary is accidentally short circuited.
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging •...
A 1200 kVA, 2.3 kV, 3-phase, star - connected alternator has a resistance of 0.401 /phase...
A 1200 kVA, 2.3 kV, 3-phase, star - connected alternator has a resistance of 0.401 /phase and a synchronous reactance of 3.21 /phase. If the generator is supplying a load at a power factor of 0.8 lagging and at rated KVA, calculate the change in line voltage at the output terminals of the generator if the load is suddenly disconnected. Assume the speed and the excitation current is to remain unchanged.
A 10-kVA, 250 / 100-V, 50-Hz single-phase transformer gave the following open and short circuit test...
A 10-kVA, 250 / 100-V, 50-Hz single-phase transformer gave the following open and short circuit test results: Open circuit test: 250 V, 2.6 A, power factor: 0.3 on HV side. Short circuit test: 18 V, 80 A, input power: 240 W on HV side. Calculate the following: 4.1 The equivalent circuit parameters of the transformer. (6) 4.2 The efficiency at full load unity power factor. (NB the test current is not at full load) (6) 4.3 The load at which...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance of 6.08 Ohms as referred to its high-voltage terminals. The transformer is supplying a load of 375 MVA, with 0.89 power factor lagging at a voltage of 24 kV (line-to-line) on its low-voltage side. It is supplied from a feeder whose impedance is 0.17 + j 2.2 Ohms connected to its high-voltage terminals. The total load in the system remains constant at 375 MVA....
A 2.2 KVA, 440---220 V, 60 Hz, step-down transformer has the following parameters: Rp= 3.0 Ω,...
A 2.2 KVA, 440---220 V, 60 Hz, step-down transformer has the following parameters: Rp= 3.0 Ω, Xp= 4.0 Ω, Rs= 2.5 Ω, Xs= 2.0 Ω, Rc= 60 KΩ, and Xm = 15 KΩ. The transformer is operating at full load with a power factor of 0.707 lagging. The magnetizing branch impedance can be ignored. a) Draw the transformer’s equivalent T-circuit, b) Find the equivalent winding impedance referred to the high side, c) Calculate the primary and secondary currents, d) Determine...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance,...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance, Xs = 17.9, and is connected to an infinite bus at rated voltage. If the rotational and electrical losses are negligivle, what is Ia, Ef, delta, theta, Tdrive, Phasor diagram, and power flow diagram (label completely with numerical values for, A) the machine as a generator; the prime-throttle is opened and If is adjusted so that the machine delivers rated kVA, 0.8 pf lagging,...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT