Question

Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V,...

Plate values ​​of a three-phase transformer are given below:
1600 kVA, 15 kV / 400 V, 50 Hz, io = 1.2%; ukN = 6%, idle losses 2450 W, rated
copper losses of power 14500 W; Dy5.
a) Calculate primary and secondary line and phase currents.
b) Secondary at 75% load in power factor with 0.85 inductance and 0.85 capacity
calculate the voltage separately. Compare and interpret the results. capacity
at what time of day can the upload be seen? To prevent voltage change
What solution should be applied?
c) Calculate the rated operating efficiency and maximum efficiency of the transformer.
d) Draw the fastening group. How is this transformer parallel with the transformer Dy11 connected
run?
e) If this transformer is operated at 60 Hz, which sizes change how?
Your review.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V,...
Plate values ​​of a three-phase transformer are given below: 1600 kVA, 15 kV / 400 V, 50 Hz, io = 1.2%; ukN = 6%, idle losses 2450 W, rated copper losses of power 14500 W; Dy5. a) Calculate primary and secondary line and phase currents. b) Secondary at 75% load in power factor with 0.85 inductance and 0.85 capacity calculate the voltage separately. Compare and interpret the results. capacity at what time of day can the upload be seen? To...
Plate values of a three-phase transformer are given below: 1600 kVA, 15 kV / 0,4 kV,...
Plate values of a three-phase transformer are given below: 1600 kVA, 15 kV / 0,4 kV, 50 Hz, i0 = 1.2%; ukN= 6%, idle losses 2450 W, rated power copper losses 14500 W; Dy5 connected.. III) There is 75% load in the power factor with 0.85 inductance and 0.85 capacity. At what times of the day can capacity loading be seen? What solution should be applied to prevent voltage change? IV) Draw the fastening group. How can this transformer be...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is...
A Wye-Delta transformer is connected to a 66 kV input three-phase transmission line. Each transformer is rated at 1000 kVA and has a step-down ratio of 8:1. The bank supplies a balance load having a power factor of 0.8 lag with a load current of 70 A. Assume ideal transformer, determine. The primary line and phase voltages The secondary line and phase voltages The secondary line and phase currents The apparent and active power at the load Total kVA capacity...
A single phase transformer rated at 3000 KVA, 69kV, 60 Hz has a total internal impedance...
A single phase transformer rated at 3000 KVA, 69kV, 60 Hz has a total internal impedance Zp of 127ohm, referred to the primary side. Calculate: a) primary and secondary currents b) voltage regulation from no load to full load for 2000 kW resistive load, knowing that the primary voltage supply is fixed at 69 kV. c) primary and secondary currents if the secondary is accidentally short circuited.
A single phase 60 Hz two-winding power transformer is rated at 2400V/240V and 100 kVA. If...
A single phase 60 Hz two-winding power transformer is rated at 2400V/240V and 100 kVA. If an autotransformer is built from this conventional transformer to supply a load at 2400V with supply voltage 2640V. Draw the autotransformer and calculate the voltage, current and apparent power rating of the auto transformer. Also calculate the apparent power rating advantage of autotransformer over conventional transformer.
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging •...
A 1200 kVA, 2.3 kV, 3-phase, star - connected alternator has a resistance of 0.401 /phase...
A 1200 kVA, 2.3 kV, 3-phase, star - connected alternator has a resistance of 0.401 /phase and a synchronous reactance of 3.21 /phase. If the generator is supplying a load at a power factor of 0.8 lagging and at rated KVA, calculate the change in line voltage at the output terminals of the generator if the load is suddenly disconnected. Assume the speed and the excitation current is to remain unchanged.
Three 1-φ, 100 kVA, 1730/208 V, 60 Hz transformer are connected to form a 3-φ1730/480 V...
Three 1-φ, 100 kVA, 1730/208 V, 60 Hz transformer are connected to form a 3-φ1730/480 V transformer bank. The equivalent impedance of each transformer referred to the high voltage side is 0.3 + j0.4 ohms. The transformer delivers 40 kW to the load at 0.8 p.f. leading. a) Determine the phase and the line currents at the primary and the secondary sides. b) Draw the equivalent per-phase circuit refereed to the primary side and determine the primary volt
Three 1-φ, 100 kVA, 1730/208 V, 60 Hz transformer are connected to form a 3-φ1730/480 V...
Three 1-φ, 100 kVA, 1730/208 V, 60 Hz transformer are connected to form a 3-φ1730/480 V transformer bank. The equivalent impedance of each transformer referred to the high voltage side is 0.3 + j0.4 ohms. The transformer delivers 40 kW to the load at 0.8 p.f. leading. a) Determine the phase and the line currents at the primary and the secondary sides. b) Draw the equivalent per-phase circuit refereed to the primary side and determine the primary volt
A 10-kVA, 250 / 100-V, 50-Hz single-phase transformer gave the following open and short circuit test...
A 10-kVA, 250 / 100-V, 50-Hz single-phase transformer gave the following open and short circuit test results: Open circuit test: 250 V, 2.6 A, power factor: 0.3 on HV side. Short circuit test: 18 V, 80 A, input power: 240 W on HV side. Calculate the following: 4.1 The equivalent circuit parameters of the transformer. (6) 4.2 The efficiency at full load unity power factor. (NB the test current is not at full load) (6) 4.3 The load at which...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT