A 3 phase, 3.3 kV industrial plant has an overall power factor
of 0.88 lagging. A 200 kVA synchronous motor is added to the system
and is run at zero power
factor and slightly reduced rating to provide power factor
correction only. The total load is then 350 kVA at unity power
factor. It was then decided to run the synchronous machine at its
rated kVA and use it as a source of mechanical power, what gross
mechanical power would it produce
with the overall power factor of the installation at:
1. unity and
2. reduced to 0.96 lagging.
Answer: 1 65.67 kW; 2 197.87 kW]