Question

A 200kVA, 480v, 50Hz, star connected synchronous generator with a rated field current of 5A was...

A 200kVA, 480v, 50Hz, star connected synchronous generator with a rated field current of 5A was tested at rated speed and the following data were taken:

1. The open circuit terminal voltage of the generator was 540v at rated field current.

2. The short circuit line current was 300A at rated current.

3. With the machine at standstill, a dc voltage of 10v was applied between two of the generator terminals, a current of 25A was measured.

Determine the values of the armature reactance and the synchronous reactance for the generator equivalent circuit.

Homework Answers

Answer #1

If you have any doubts please feel free to ask me..

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of 1.33 p.u. The generator achieves rated open circuit voltage at a field current of 325 A. The generator is connected to a network with an equivalent line-line voltage of 11 kV and an equivalent impedance of 0.17 pu on the generator base. The generator is loaded to a real power of 110 MW. a- Find the generated voltage Eaf in p.u. such that the...
A three-phase Wye-connected synchronous generator is rated 3600 rpm, 200kVA, 480V, 60 Hz. The generator’s armature...
A three-phase Wye-connected synchronous generator is rated 3600 rpm, 200kVA, 480V, 60 Hz. The generator’s armature winding resistance is RA = 0.03Ω and the synchronous reactance XS is 0.25Ω. The rotational losses are 6kW, the core losses are 4kW, and the stray losses are 1% of the output real power. The generator is delivering 200kVA power at 0.85 pf lagging at rated voltage. Taking the phase voltage at the output as a reference, answer the following questions. How many poles...
A 3-phase, 40 MVA, 13.8 kV, 60 Hz, ?-connected alternator requires field current of 250 A...
A 3-phase, 40 MVA, 13.8 kV, 60 Hz, ?-connected alternator requires field current of 250 A to produce an open circuit rated voltage while a field current of 150 A is required to produce short circuit rated armature current. Neglect armature resistance. Determine the Synchronous Reactance (Xs).
The test results of a three-phase synchronous generator with the rated voltage of 6,600V and the...
The test results of a three-phase synchronous generator with the rated voltage of 6,600V and the capacity of 50 MVA are as follows. No-load test result: When the terminal voltage was 6,600V, the field current was 1280A. Short circuit test result: The field current required to flow the rated current was 1600A. Find the rated current of this generator Find the short-circuit ratio. However, the second decimal shall be rounded off to obtain the first decimal Find the synchronous reactance....
A balanced, symmetrical, round-rotor, 3-phase, 60 Hz, 2-pole, 100MVA, 13.8kV, synchronous generator is being driven at...
A balanced, symmetrical, round-rotor, 3-phase, 60 Hz, 2-pole, 100MVA, 13.8kV, synchronous generator is being driven at synchronous speed. During tests, an IFNL (field current required to produced rated terminal voltage under open circuit) of 150A and an IFSC (field current required to produced rated armature current under short circuit) of 100A were obtained. Use a linear model and neglect the armature resistance for the following calculations. a) What field current is needed to maintain rated terminal voltage when the generator...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA at a FP = 0.8 lagging with a line voltage of 450-V. The machine stator resistance RS = 0.004 ?. The synchronous reactance is Xs=0.08 ?. The actual system load on the machine draws 900 kW at FP = 0.6 lagging. Assume that a voltage regulator has automatically adjusted the field current so that the terminal voltage is its rated value. Mechanical losses are...
A synchronous generator and motor are rated 30,000kVA, 13.2kV, and both have subtransient reactances of 20%....
A synchronous generator and motor are rated 30,000kVA, 13.2kV, and both have subtransient reactances of 20%. The line connecting them has a reactance of 10% on the base of the machine ratings. The motor is drawing 20,000kW at 0.8 power-factor leading and a terminal voltage of 12.8kV when a symmetrical three phase fault occurs at the generator terminals. Find A synchronous generator and motor are rated 30,000kVA, 13.2kV, and both have subtransient reactances of 20%. The line connecting them has...
3) A three-phase, nozzle, 4-pole cylindrical pole synchronous generator feeds a 400 Volt, 50Hz conversion center....
3) A three-phase, nozzle, 4-pole cylindrical pole synchronous generator feeds a 400 Volt, 50Hz conversion center. The synchronous reactance of the synchronous generator is 0.72 Ove armature resistance is neglected. The relation between the pole voltage E 'induced in the induction of the synchronous generator and the excitation current, is selected as E, = 824. In this working environment of the synchronous generator, a.) On the consumer screen, find the excitation current (U), load values, internal phase values, the moment...
A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a...
A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a synchronous reactance of 3.0 Ω. Its efficiency at full load is 89% (1 Hp=746 watt). (a) What is the line current of the generator at rated conditions? (b) What is the internal generated voltage EA of this motor at rated conditions?
Two dc generators (A) and (B) with the following characteristics: Generator (A): rated voltage = 150...
Two dc generators (A) and (B) with the following characteristics: Generator (A): rated voltage = 150 V, rated current = 30 Amp, and armature resistance = 0.4 Ω. Generator (B): no-load voltage = 160 V, rated current = 20 Amp, and armature resistance = 0.6 Ω. are connected in parallel. Find: a) Circulating no-load current and terminal voltage. b) The load current when generator B floating. c) The maximum possible load power