Question

100 60 W incandescent lamps will be replaced by 32 W fluorescent lamps. Compute the savings...

100 60 W incandescent lamps will be replaced by 32 W fluorescent lamps. Compute the savings in air conditioning energy that this replacement will enable if the building air conditioning runs 4500 hours/year. The air conditioner has a COP=2.8.

Homework Answers

Answer #1

Effect of bulbs on Air-Conditioning: When bulbs are glowing, most of the electrical energy is converted into heat and some amount of electrical energy is utilized to provide light. So when we use glowing bulbs in an air-conditioning room, the heat from bulbs will result in increase in room temperature and thus require air-conditioners to work more for maintaining colder temperatures. Therefore, glowing bulbs will increase load on air-conditioners.

Let me explain the question as a situation.

There are 100 incandescent lamps. Each incandescent lamp consumes power of 60Watts. Now we are replacing all these incandescent lamps by fluorescent lamps. Each fluorescent lamp consumes only 32Watts. Observe that there is a decrease in power consumption due to replacement of bulbs. The decrease in power consumption = (60 - 32) = 28Watts per bulb. As we are replacing all the 100 bulbs, the total decrease in power consumption is 28*100 = 2800Watts = 2.8KW.

  • We can say that total KW savings = 2.8KW.

The decrease in heat generation by lamps will reduce work load on air-conditioners. Given Coefficient Of Performance (COP) of air-conditioner is 2.8

Now the air-conditioner savings are given by :

  • Air-conditioner savings =
  • = (2.8 * 4500)/(2.8) = (12600)/(2.8) = 4500 KWh per year

Therefore the answer is 4500 KWh/year.

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
1.Three incandescent lamps, 60 W, 100 W, and 200 W are connected in parallel to a...
1.Three incandescent lamps, 60 W, 100 W, and 200 W are connected in parallel to a 120 V source. What is the resistance of each of the lamps and the current supplied by the 120 V source? 2. A 1500 W toaster oven and a 600 W coffee maker are connected in parallel to a 120 V source that is protected by a 20 A circuit breaker. We want to connect a blender to the same 120 V source to...
QUESTION 1 The term "Slip" indicates the difference between the motor's synchronous speed and the no-load...
QUESTION 1 The term "Slip" indicates the difference between the motor's synchronous speed and the no-load speed True False 1 points    QUESTION 2 Wet Bulb (WB) Temperature: is for the temperature reading form an ordinary mercury bulb thermometer or regular temperature sensor. True False 1 points    QUESTION 3 The refrigerant (R-134a) is the new replacement of the refrigerant (R-22) as it is less harmful to the environment. True False 1 points    QUESTION 4 Draft Gauge and Bourdon...
What tools could AA leaders have used to increase their awareness of internal and external issues?...
What tools could AA leaders have used to increase their awareness of internal and external issues? ???ALASKA AIRLINES: NAVIGATING CHANGE In the autumn of 2007, Alaska Airlines executives adjourned at the end of a long and stressful day in the midst of a multi-day strategic planning session. Most headed outside to relax, unwind and enjoy a bonfire on the shore of Semiahmoo Spit, outside the meeting venue in Blaine, a seaport town in northwest Washington state. Meanwhile, several members of...