Question

QUESTION A 60-Hz turbogeneralor is rated 500 MVA, 22 kV . It is Y-connected and solidly...

QUESTION

A 60-Hz turbogeneralor is rated 500 MVA, 22 kV . It is Y-connected and solidly
grounded and is operating at rated voltage at no load. It is disconnected from the
,rest of the system. Its reactances are Xd'' = X1 = X2 = 0.15 and Xo = 0.05 per
unit. Find the ratio of the sub transient line current for a single line-to-ground
fault to the sub transient line current for a symmetrical three-phase fault.

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A 60-Hz turbogenerator is rated 500 MVA, 22 kV. It is Y-connected and solidly grounded and...
A 60-Hz turbogenerator is rated 500 MVA, 22 kV. It is Y-connected and solidly grounded and is operating at rated voltage at no load. It is disconnected from the rest of the system. Its reactances are given below. X'' = X1 = X2 =0.15pu, and X0 = 0.05pu a ) Find the ratio of the subtransient line current for a single line-to-neutral fault to the subtransient line current for a symmetrical three-phase fault. b ) Determine the inductive reactance in...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load...
a) A three phase transformer rated at 30 MVA 10 kV(Δ)/1 kV(Y) is supplying a load at the low voltage side. The load absorbs 5 MVA, 0.7 power factor lagging at line to line voltage 0.9 kV. The transformer has an equivalent reactance 0.05 Ω/phase. Assuming 10 MVA and 1 kV as base value, draw the per unit diagram for the system. Find the Line to Line voltage at the primary side of the transformer. b) A three-phase synchronous generator...
A 3-phase, 40 MVA, 13.8 kV, 60 Hz, ?-connected alternator requires field current of 250 A...
A 3-phase, 40 MVA, 13.8 kV, 60 Hz, ?-connected alternator requires field current of 250 A to produce an open circuit rated voltage while a field current of 150 A is required to produce short circuit rated armature current. Neglect armature resistance. Determine the Synchronous Reactance (Xs).
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase...
Problem 2. A three phase transformer rated at 5 MVA, 115/13.2 kV has a per phase series impedance of 0.007 + j0.075 per unit (shunt parameters are ignored). The low voltage side is connected to a short distribution line which modeled by a series per phase impedance of 0.02 +j0.1 per unit on the base of 10 MVA. The line supplies a balanced three phase constant impedance load at 4 MVA, 13.2 kV with power factor of 0.85 lagging •...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance...
Use MATLAB: A three-phase Y-A transformer is rated 225-kV:24-kV, 400 MVA and has a series reactance of 6.08 Ohms as referred to its high-voltage terminals. The transformer is supplying a load of 375 MVA, with 0.89 power factor lagging at a voltage of 24 kV (line-to-line) on its low-voltage side. It is supplied from a feeder whose impedance is 0.17 + j 2.2 Ohms connected to its high-voltage terminals. The total load in the system remains constant at 375 MVA....
A 3 phase 11 kv,25 mva, 60 Hz salient pole synchronous motor is running from a...
A 3 phase 11 kv,25 mva, 60 Hz salient pole synchronous motor is running from a 11 Kv, 60 Hz balanced three phase supply the meachince reactances are Xd=1.2 pu and Xq=0.6 pu ,neglect the meachanicalloss and armature copper loss the maximum power input is obtained with no field excitation determine the power factor of motor
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms...
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms per phase. The machine is connected to kV, 60 Hz bus and is operated as synchronous condenser (synchronous motor at no-load condition) a. For normal excitation (excitation voltage terminal voltage), find the line current. Draw the phasor diagram b. If the excitation is increased to 150% of the normal excitation, find the line current and reactive power delivered or absorbed by the bus. Draw...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance of 30W and negligible resistance. The generator is connected to an infinite bus at 6.6 KV and 60 Hz. a)Determine the excitation voltage (Ea) when the machine is delivering rated power at o.8 PF lagging. b)The field excitation current is increased by 10% without changing the power input from the prime mover. Find the stator current (Ia), the power factor and the reactive power...
A 3? power system consists of a Y-connected source (300 MVA, 23 kV) supplying a Y-connected...
A 3? power system consists of a Y-connected source (300 MVA, 23 kV) supplying a Y-connected load (240 MVA, 230 kV, PF = 0.90 lagging) through a step-up transformer (330 MVA, 23?/230Y kV, X = 0.11 per unit). Take into account the transformer’s phase shift and choose the load terminal voltage VAN as the reference. Use base values of 100 MVA and 230 kV at the load. (a) Find the per-unit load currents (IA, IB, and IC). (b) Find the...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of 1.33 p.u. The generator achieves rated open circuit voltage at a field current of 325 A. The generator is connected to a network with an equivalent line-line voltage of 11 kV and an equivalent impedance of 0.17 pu on the generator base. The generator is loaded to a real power of 110 MW. a- Find the generated voltage Eaf in p.u. such that the...