Question

A 3-phase, Y-connected 4-wire system with grounded neutral carrying 60 A at 60 Hz per phase...

A 3-phase, Y-connected 4-wire system with grounded neutral carrying 60 A at 60 Hz per phase when balanced has 3rd harmonic current. The harmonic current is measured at 3 A/phase.

a. For this system to remain without voltage distortion, what must be the current that the neutral carries to ground? (Easy answer.)

b. The 3rd harmonic frequency is 180 Hz. If there is reactance XL = 2 Ω/phase in the line, what is the per phase capacitance (mF) of a series-connected power factor correction capacitor (measured line-neutral) in the line for there to be resonance at the harmonic frequency? [Answer: 0.442 mF,. Resonance in power factor correction capacitors is a problem in a circuit with harmonic distortion, because at resonance the only resistance in the line is the (small) resistance of the wires, causing too much current and the capacitors can overheat and burn up.]

Homework Answers

Answer #1

(a) If the system has to be undistorted in terms of voltage then the current from neutral to ground should be the value of harmonic current of the system, only because of the harmonics there is a distortion in the voltage. If the harmonic currents flow through the grounded neutral it discharges into ground and will not have any effect on the system.

Given that

harmonic current per phase (Ih) = 3A

Neutral current (In) = 3*3A = 9A

(Since the neutral carries the sum of the currents of all the phases)

Therefore, the current through the neutral to avoid the voltage distortion is 9A.

(b)

The solution to the problem (b) is shown in the above image. I hope you are satisfieed with my work.

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A 60-Hz turbogenerator is rated 500 MVA, 22 kV. It is Y-connected and solidly grounded and...
A 60-Hz turbogenerator is rated 500 MVA, 22 kV. It is Y-connected and solidly grounded and is operating at rated voltage at no load. It is disconnected from the rest of the system. Its reactances are given below. X'' = X1 = X2 =0.15pu, and X0 = 0.05pu a ) Find the ratio of the subtransient line current for a single line-to-neutral fault to the subtransient line current for a symmetrical three-phase fault. b ) Determine the inductive reactance in...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance of 30W and negligible resistance. The generator is connected to an infinite bus at 6.6 KV and 60 Hz. a)Determine the excitation voltage (Ea) when the machine is delivering rated power at o.8 PF lagging. b)The field excitation current is increased by 10% without changing the power input from the prime mover. Find the stator current (Ia), the power factor and the reactive power...
A 4- pole, 50 Hz, Y-connected, 3-phase generator has a phase voltage of 260 V ∠0°,...
A 4- pole, 50 Hz, Y-connected, 3-phase generator has a phase voltage of 260 V ∠0°, a synchronous reactance of 0.06 Ω, a stator resistance of 0.003 Ω, and Lsf= 0.02 H. The generator is directly connected to a balanced 3-phase load that draws 2 MW at a lagging 0.8 power factor. Sketch the equivalent circuit annotating all the components, currents and voltages on the diagram Calculate the 3-phase apparent power of the load in rectangular form Calculate the generator...
A 42 kVA three-phase synchronous generator with line voltage 4.16 kV at a frequency of 60...
A 42 kVA three-phase synchronous generator with line voltage 4.16 kV at a frequency of 60 Hz, is connected in star configuration. The generator has a winding whose armature resistance is 0.8 Ω and a synchronous reactance of 7.4 Ω, both per phase. Determine the voltage regulation when the power factor is 0.600 lagging.
A 3-phase, 40 MVA, 13.8 kV, 60 Hz, ?-connected alternator requires field current of 250 A...
A 3-phase, 40 MVA, 13.8 kV, 60 Hz, ?-connected alternator requires field current of 250 A to produce an open circuit rated voltage while a field current of 150 A is required to produce short circuit rated armature current. Neglect armature resistance. Determine the Synchronous Reactance (Xs).
4) A three-phase synchronous motor of 4000 hp nominal, 13,200 V, 60 Hz, 2 poles, connected...
4) A three-phase synchronous motor of 4000 hp nominal, 13,200 V, 60 Hz, 2 poles, connected in star, operating at 0.84 of power factor in advance, has an efficiency of 96.5%. The synchronous reactance per phase is 49.33 Ω: • Draw the phasor diagram on the grid sheet • Determine the loading angle • Determine the load torque
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms...
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms per phase. The machine is connected to kV, 60 Hz bus and is operated as synchronous condenser (synchronous motor at no-load condition) a. For normal excitation (excitation voltage terminal voltage), find the line current. Draw the phasor diagram b. If the excitation is increased to 150% of the normal excitation, find the line current and reactive power delivered or absorbed by the bus. Draw...
QUESTION A 60-Hz turbogeneralor is rated 500 MVA, 22 kV . It is Y-connected and solidly...
QUESTION A 60-Hz turbogeneralor is rated 500 MVA, 22 kV . It is Y-connected and solidly grounded and is operating at rated voltage at no load. It is disconnected from the ,rest of the system. Its reactances are Xd'' = X1 = X2 = 0.15 and Xo = 0.05 per unit. Find the ratio of the sub transient line current for a single line-to-ground fault to the sub transient line current for a symmetrical three-phase fault.
Two parallel loads are connected to a 220-V, 60 Hz, single-phase source where the first load...
Two parallel loads are connected to a 220-V, 60 Hz, single-phase source where the first load consumes power 100kW at power factor 1 and the second load consumes 100kW at power factor 0.8 lagging. By placing a bank of capacitors in parallel with the load, the resultant power factor is to be raised to 0.98 lagging. (a) Find the net capacitance of the capacitor bank in µF that is required. (b) Simulate the circuit in Matlab and verify your result.
A three phase Y connected synchronous motor has negligible armature resistance and a synchronous reactance of...
A three phase Y connected synchronous motor has negligible armature resistance and a synchronous reactance of 12 ohm/phase. The motor takes 12,000kW at a line voltage of 13,200V. If the line current is adjusted so that the excitation voltage is 9000V/phase: a. What is the torque angle? b. At what power factor is the motor operating? c. What is its armature current?
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT