Question

A 3 phase 11 kv,25 mva, 60 Hz salient pole synchronous motor is running from a...

A 3 phase 11 kv,25 mva, 60 Hz salient pole synchronous motor is running from a 11 Kv, 60 Hz balanced three phase supply the meachince reactances are Xd=1.2 pu and Xq=0.6 pu ,neglect the meachanicalloss and armature copper loss the maximum power input is obtained with no field excitation determine the power factor of motor

Homework Answers

Answer #1

Ans:

Recall the equation of active power in salient pole syncronous motor.

Here,

is excitation emf.

is terminal voltage per phase.

is d-axis reactance.

is q-reactance.

is power angle.

It is given that field excitation is zero.

Power is maximum , therefore value of should be maximum.

i.e.

Now recall the equation of reactive power of a syncronous motor working at lagging power factor.

Put

  

  

   

Put

  

  

Let    is power factor angle.

power factor   lagging

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms...
A 3-phase, 5 MVA, kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms per phase. The machine is connected to kV, 60 Hz bus and is operated as synchronous condenser (synchronous motor at no-load condition) a. For normal excitation (excitation voltage terminal voltage), find the line current. Draw the phasor diagram b. If the excitation is increased to 150% of the normal excitation, find the line current and reactive power delivered or absorbed by the bus. Draw...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance...
A 3-phase, 1.2 MVA, Y-connected, 6.6 KV, 6-poles, 60 HZ, synchronous generator has a synchronous reactance of 30W and negligible resistance. The generator is connected to an infinite bus at 6.6 KV and 60 Hz. a)Determine the excitation voltage (Ea) when the machine is delivering rated power at o.8 PF lagging. b)The field excitation current is increased by 10% without changing the power input from the prime mover. Find the stator current (Ia), the power factor and the reactive power...
A three phases, 6 MVA, 22 kV, 60 Hz synchronous machine has a synchronous reactance of...
A three phases, 6 MVA, 22 kV, 60 Hz synchronous machine has a synchronous reactance of 10 ohms per phase and has negligible stator resistance. The machine is connected to the 22 kV, 60 Hz bus and is operated as a synchronous condenser, Neglect rotational losses 7 a) For normal excitation, find the stator current. Draw the phasor diagram. b) If the excitation is increased to 120 percent of the normal excitation, find the stator current and power factor, draw...
A 3-phase, 40 MVA, 13.8 kV, 60 Hz, ?-connected alternator requires field current of 250 A...
A 3-phase, 40 MVA, 13.8 kV, 60 Hz, ?-connected alternator requires field current of 250 A to produce an open circuit rated voltage while a field current of 150 A is required to produce short circuit rated armature current. Neglect armature resistance. Determine the Synchronous Reactance (Xs).
A salient-pole synchronous machine with negligible armature resistance has the following parameters all expressed in the...
A salient-pole synchronous machine with negligible armature resistance has the following parameters all expressed in the per unit system: xd =Lis, Xq = 0.95 The machine is connected to a transmission line represented by: A = 0.98L0.2°, B = 0.2L85° The load at the end of the line draws a current of 1 pu at a voltage of 1 pu. The load power factor is unity. Calculate the apparent power output of the machine. a-. Calculate the required excitation voltage...
A two-pole Y-connected generator rated at 13.8 kV, 20 MVA, 0.8 p.f. leading is running at...
A two-pole Y-connected generator rated at 13.8 kV, 20 MVA, 0.8 p.f. leading is running at 1800 rpm. The generator has a synchronous reac- tance of 8 Ω per phase (at 60 Hz) and a negligible armature resistance per phase. The generator is operated in parallel with an interconnected power network. Compute the following: (i) What is the torque angle of the generator at rated conditions? (ii) How many MW of power this generator can deliver?
(360) Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole -connected synchronous motor has 0.9Ω synchronous reactance....
(360) Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole -connected synchronous motor has 0.9Ω synchronous reactance. Friction; wind; core losses and armature resistance are neglected. a) If the motor is operating under magnitude of phase current (ia) (180) Ampere and power factor of 0.6 lagging, 1. Find the input power of motor in hp 2. Find the generated voltage, EA 3. Find the torque and the maximum inducible torque in current state. b) If EA is increased by 18% find,...
410 Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole Triangle connected synchronous motor has 0.9Ω synchronous...
410 Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole Triangle connected synchronous motor has 0.9Ω synchronous reactance. Friction; wind; core losses and armature resistance are neglected. a) If the motor is operating under magnitude of phase current (ia) 230 Ampere and power factor of 0.6 lagging, 1. Find the input power of motor in hp (10p) 2. Find the generated voltage, EA (10p) 3. Find the torque and the maximum inducible torque in current state. (10p) b) If EA is...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of...
A 125 MVA 11 kV three phase 50 Hz synchronous generator has a synchronous reactance of 1.33 p.u. The generator achieves rated open circuit voltage at a field current of 325 A. The generator is connected to a network with an equivalent line-line voltage of 11 kV and an equivalent impedance of 0.17 pu on the generator base. The generator is loaded to a real power of 110 MW. a- Find the generated voltage Eaf in p.u. such that the...
Determine the kinetic energy stored by a 300 MVA, 60 Hz, two pole synchronous generator with...
Determine the kinetic energy stored by a 300 MVA, 60 Hz, two pole synchronous generator with an inertia constant H of 5.66 MJ/MVA. Assume the machine is running steadily at synchronous speed with a shaft input of 366000 hp. The electrical power developed suddenly changes from its normal value to a value of 200 MW. a. Determine the acceleration or deceleration of the rotor. b. If the acceleration computed for the generator is constant for a period of 10 cycles,...