Question

20-pole, 200 hp, 660 V, 60 Hz, Y-connected, three-phase synchronous motors are operating at no load....

20-pole, 200 hp, 660 V, 60 Hz, Y-connected, three-phase synchronous motors are operating at no load.
The rotor lags 0.5 degrees to the magnetic flux of the rotor with a mechanical angle,
with the induced equipment power adjusted to the same magnitude
as the phase voltage applied to the armature.
The synchronous reactance is 10 ohms and the armature resistance is 1 ohms.
Find
a) The load angle of the rotor expressed in electrical angles.
b) Armature current
c) Equivalent power and full input power.
d) Armature loss and rotational loss.

answer
a) 5 deg
b) 3.31 A
c) 1,261W, 3,783W
d) 33W, 3,750W

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
a 460-V 100-hp 60-Hz 4 pole Y connected synchronous motor has a operating power factor 0.85...
a 460-V 100-hp 60-Hz 4 pole Y connected synchronous motor has a operating power factor 0.85 leading the aramature resistance is o.2 ohms and synchronous reactance is 12 ohms at full load the efficiency is 85% find the sum of mechanical loss core loss and stray loss when meachine is operating at full load
A 100 hp, three-phase, 60Hz, 460V, four-pole, Y-connect synchronous motor is operating leading at 0.8 p.f....
A 100 hp, three-phase, 60Hz, 460V, four-pole, Y-connect synchronous motor is operating leading at 0.8 p.f. at rated conditions. Excluding field and stator losses, the efficiency is 96% and the synchronous reactance is 2.72ohm. Find a) Induced torque b) Armature current c) Internal induced electromotive force and power angle. d) Maximum load that can be driven by this electric motor. answer a) 412.2 N-m b) 121.9 A c) 535.5 V, 29.7 deg d) 153.8 kW
4) A three-phase synchronous motor of 4000 hp nominal, 13,200 V, 60 Hz, 2 poles, connected...
4) A three-phase synchronous motor of 4000 hp nominal, 13,200 V, 60 Hz, 2 poles, connected in star, operating at 0.84 of power factor in advance, has an efficiency of 96.5%. The synchronous reactance per phase is 49.33 Ω: • Draw the phasor diagram on the grid sheet • Determine the loading angle • Determine the load torque
(360) Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole -connected synchronous motor has 0.9Ω synchronous reactance....
(360) Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole -connected synchronous motor has 0.9Ω synchronous reactance. Friction; wind; core losses and armature resistance are neglected. a) If the motor is operating under magnitude of phase current (ia) (180) Ampere and power factor of 0.6 lagging, 1. Find the input power of motor in hp 2. Find the generated voltage, EA 3. Find the torque and the maximum inducible torque in current state. b) If EA is increased by 18% find,...
A three phase, 200 kW, 2300 V, 50 Hz star (wye) connected non-salient rotor synchronous motor...
A three phase, 200 kW, 2300 V, 50 Hz star (wye) connected non-salient rotor synchronous motor has a synchronous reactance of 11 Ohms per phase. When it draws 175 kW the power angle is 10 electrical degrees. Neglect the ohmic losses. a. Determine the excitation voltage per phase. b. Calculate the supply line current. c. Determine the supply power factor. d. Draw the phasor diagram. e. By what percentage should the field current be changed to minimize the line current.
410 Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole Triangle connected synchronous motor has 0.9Ω synchronous...
410 Volt, 60 Hz, 600 hp, 0.6 pf-leading, four-pole Triangle connected synchronous motor has 0.9Ω synchronous reactance. Friction; wind; core losses and armature resistance are neglected. a) If the motor is operating under magnitude of phase current (ia) 230 Ampere and power factor of 0.6 lagging, 1. Find the input power of motor in hp (10p) 2. Find the generated voltage, EA (10p) 3. Find the torque and the maximum inducible torque in current state. (10p) b) If EA is...
A 208 V 10 Hp four pole 60 Hz Y connected induction motor has a full...
A 208 V 10 Hp four pole 60 Hz Y connected induction motor has a full load slip of 5%. What is the output power of this motor in kW? If friction and windage loss is 350 watts, what is the gross mechanical output at full load? What is the gross torque of this motor at full load? What is the rotor cupper loss at full load? If the efficiency of this motor is 90% at full load what is...
A three-phase, 280 V, 60 Hz, 20 hp, 1710 r/m. Y-connected induction motor has the following...
A three-phase, 280 V, 60 Hz, 20 hp, 1710 r/m. Y-connected induction motor has the following impedances in ohms per phase referred to the stator circuit: R1=0.12 Ω.                Rˈ2=0.1 Ω X1=Xˈ2=0.25 Ω        Xm=10 Ω A total rotational loss are 400 W. The core loss is lumped in with the rotational losses. For a slip of 0.05 at the rated voltage and rated frequency. Find: a) The numbers of poles of the motor. b) The stator current. c) the power factor...
The following test data apply to a 7.5-hp, three-phase, 220-V, 19-A,60-Hz, four-pole induction motor with a...
The following test data apply to a 7.5-hp, three-phase, 220-V, 19-A,60-Hz, four-pole induction motor with a double-squirrel-cage rotor of design class C (high-starting-torque, low-starting current type): Test 1: No-load test at 60 Hz; Applied voltage V = 219 V line-to-line; Average phase current I1,nl = 5.70 A; Power Pnl =380 W; Test 2: Blocked-rotor test at 15 Hz; Applied voltage V = 26.5 V line-to-line; Average phase current ll,bl = 18.57 A; Power Pbl = 675 W; Test 3: Average...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance,...
A three-phase, 9,375 kVA, 13.8 kV, 4-pole, 60 Hz, Y-connected synchronous generator has a synchronous reactance, Xs = 17.9, and is connected to an infinite bus at rated voltage. If the rotational and electrical losses are negligivle, what is Ia, Ef, delta, theta, Tdrive, Phasor diagram, and power flow diagram (label completely with numerical values for, A) the machine as a generator; the prime-throttle is opened and If is adjusted so that the machine delivers rated kVA, 0.8 pf lagging,...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT