Two dc generators (A) and (B) with the following characteristics: Generator (A): rated voltage = 150...

Two dc generators (A) and (B) with the following characteristics: Generator (A): rated voltage = 150 V, rated current = 30 Amp, and armature resistance = 0.4 Ω. Generator (B): no-load voltage = 160 V, rated current = 20 Amp, and armature resistance = 0.6 Ω. are connected in parallel. Find: a) Circulating no-load current and terminal voltage. b) The load current when generator B floating. c) The maximum possible load power

Homework Answers

Know the answer?
Your Answer:

Post as a guest

Your Name:

What's your source?

Earn Coins

Coins can be redeemed for fabulous gifts.

Not the answer you're looking for?
Ask your own homework help question
Similar Questions
A permanent magnet DC generator is run at a constant speed of 800 rpm and provides...
A permanent magnet DC generator is run at a constant speed of 800 rpm and provides a terminal voltage of 150 V at its rated loading. Its armature resistance is Ra=0.2 Ω. When the generator is not loaded, the input power is 300W and Vt= 165V. a) Calculate the voltage regulation of the generator. b) Calculate the armature current. For the same machine given assume now that it is loaded with a load of RL= 0.35 Ω. c) Calculate the...
A 200 V DC, 1,800 RPM shunt connected motor has an armature resistance of 0.4 ohm...
A 200 V DC, 1,800 RPM shunt connected motor has an armature resistance of 0.4 ohm and a brush resistance of 0.4 ohm; brush voltage drop of 6.0 V, independent of load. The resistance of the shunt field is 230 ohm. The full load rated line current is 40 A. When the motor is operated at no load the line current is 5 A and the speed is 1750 RPM. Calculate speed at rated load Calculate speed at .3 rated...
A separate excited DC motor is running at 1000 rpm when the armature voltage is 600...
A separate excited DC motor is running at 1000 rpm when the armature voltage is 600 V. The motor has a field constant Kphi = 4 V.sec and the armature resistance of the motor is 0.8 Ohms. i. Calculate the value of the resistance of the dynamic braking at full load. The armature current should be limited to 200 % of the rated value. ii. If the motor operates in regenerative braking at a speed of 1200 rpm, calculate the...
Q3: (a) Determine the terminal voltage of a dc shunt generator which develops an e.m.f. of...
Q3: (a) Determine the terminal voltage of a dc shunt generator which develops an e.m.f. of 240V and has an armature current of 50 A on load. Assume the armature resistance is 0.04Ω. [3 marks] (b) A lap wound armature is used in a 4-pole dc machine and 70 coils on the armature each containing 10 turns. The flux per pole in the machine is 40 mWb and the machine rotates at 500 rpm; (a) How many current paths are...
A 152 V DC shunt motor has an armature resistance of 0.3ohm, a brush voltage drop...
A 152 V DC shunt motor has an armature resistance of 0.3ohm, a brush voltage drop of 2 V, the rated full load current is 70 A. A) calculate the current at the instant of starting as a percentage of full load current B) calculate the value of starting resistance of limit the motor current at the instant of starting to 150 percent of the rated load current
  A simple power system consists of a dc generator connected to a load center via a...
  A simple power system consists of a dc generator connected to a load center via a transmission line. The load resistance is 10 Ω. The transmission line is 50 km copper wire of 3 cm in diameter. If the voltage at the generator terminals is 400 V, compute the following: a.   Voltage across the load b.   Voltage drop across the line c.   Line losses d.   System efficiency
A 230 V, 250 rpm, 100 A separately excited dc motor has an armature resistance of...
A 230 V, 250 rpm, 100 A separately excited dc motor has an armature resistance of 0.5 Ω. The motor is connected to 230 V dc supply and rated dc voltage is applied the field winding. It is driving a load whose torque-speed characteristic is given by TL = 500 − 10ω where ω is the speed in rad/sec and TL is the load torque in N-m. Find (a) the steady state speed at which the motor will drive the...
A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a...
A 75-kW, 440-V, 0.8-PF-leading Y-connected synchronous generator has an armature resistance of 0.22 Ω and a synchronous reactance of 3.0 Ω. Its efficiency at full load is 89% (1 Hp=746 watt). (a) What is the line current of the generator at rated conditions? (b) What is the internal generated voltage EA of this motor at rated conditions?
A 200kVA, 480v, 50Hz, star connected synchronous generator with a rated field current of 5A was...
A 200kVA, 480v, 50Hz, star connected synchronous generator with a rated field current of 5A was tested at rated speed and the following data were taken: 1. The open circuit terminal voltage of the generator was 540v at rated field current. 2. The short circuit line current was 300A at rated current. 3. With the machine at standstill, a dc voltage of 10v was applied between two of the generator terminals, a current of 25A was measured. Determine the values...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA...
A submarine has a 3-phase, Y-connected, 2- pole, 60Hz synchronous generator rated to deliver 1687.5 kVA at a FP = 0.8 lagging with a line voltage of 450-V. The machine stator resistance RS = 0.004 ?. The synchronous reactance is Xs=0.08 ?. The actual system load on the machine draws 900 kW at FP = 0.6 lagging. Assume that a voltage regulator has automatically adjusted the field current so that the terminal voltage is its rated value. Mechanical losses are...
ADVERTISEMENT
Need Online Homework Help?

Get Answers For Free
Most questions answered within 1 hours.

Ask a Question
ADVERTISEMENT