The ABC Widget Company is billed for 190000 kWh and
registers a peak demand of 400 kVA in May 2003. The power factor
for the factory is 1. For the month the load factor is
65.97 %
63.84 %
72.1 %
62.4 %
________________________
An Absorption chiller system with COP of 0.8 is powered by hot
water that enters at 90 ºC and leaves at 80 ºC at a rate of 2 L/s
(LPS) . The chilled water operates on a 5 ºC temperature difference
and the condenser water on a 10 ºC temperature difference.
Calculate the water flow in L/s (LPS)
1.6 L/s
3.2 L/s
3.6 L/s
2.4 L/s
____________________________