A 24 in. x 16 in. column on the second floor of a multi-story building is to be designed to carry a live load of 500,000 lb, and a dead load that is 75 % of the live load (includes self weight). The nominal moment is calculated to be 5,769 kip.in. Use the interaction diagrams with γ = 0.8 to design the column reinforcement for a concrete strength of 4000 psi and a steel strength of 60000 psi. Include the detail of the ties in your design.
Step 1:
L.L=500 kips
D.L=500x0.75=375 kips
Pu=1.2(375)+1.6(500)=1250 kips
Step 2:
Mu=5769 in-kips
e=Mu/Pu=5769/1250
e=4.61 in
Step 3:
Pn=1250/0.65=1923 kips
Kn=Pn/fcAg
Kn=1923/(4x24x16)
Kn=1.25
Step 4:
Rn=Pne/(fcAgh)
Rn=1250x4.61/(4x24x16x24)
Rn=0.1563
Now from the interaction charts
=0.8
Step 5:
=0.05
Ast=0.043x16x24=16.512 in2
Provide bar no 14, 8 in number
Step 5:
Now check for lateral ties:
Assuming #3 bars
(a) Spacing=48x3/8=18 in
(b) 16x14/18=12.44 in
(c) L.L.D=16 in
Provide #3 ties with spacing of 12.4 in