A column has fixed boundary conditions at the bottom ends for weak-axis buckling and pinned boundary conditions at both ends for strong-axis buckling. Is a HSS10x8x1/2 (A500 Gr. B, Fy=46 ksi adequate for L=20’ and Pu=500 kips?
Given:
L=20 ft
Le=0.707L=14.14 ft (As column is fixed at one end and hinged at the other end)
Ultimate load Pu=500 kips
Fy=46 ksi
Step 1:
Calculate the slenderness ratio of the HSS beam
KL/ry=14.14x12/3.14
KL/ry=54.03<200
4.71(E/Fy)0.5=4.71(29000/50)0.5=118
As,KL/r<4.71(E/Fy)0.5, use AISC equation E3-2
Step 2:
Calculate the critical stress
Fe=2E/(KL/r)2
Fe=3.14x3.14x29000/(54.03)2
Fe=97.94 ksi
Fcr=0.658Fy/Fe
Fcr=(0.65846/97.94x46)=37.94 ksi
Step 3:
Calculate the nominal strength of HSS
Pn=FcrAg
Pn=37.94x15.3
Pn=580.5 kips
As per LRFD design capacity=0.9x580.5=522 kips
The HSS10x8x0.5 is enough to resist a load of 500 kips