For an infiltration rate of 1.32 air changes per hour (ACH), determine sensible, latent, and total infiltration heat load of a building at sea level, in kW, that is 20 m long, 13 m wide, and 3 m high when the outdoor air is at 32°C and 35 percent relative humidity. The building is maintained at 24°C and 55 percent relative humidity at all times. The gas constant and the specific heat of air are R = 0.287 kPa·m3/kg·K and cp = 1.005 kJ/kg·°C, respectively. Use data from the tables.
The sensible infiltration heat load of the room is kW.
The latent infiltration heat load of the room is kW.
The total infiltration heat load of the room is kW.
Given: building temperature
relative humidity
ambient temperature
relative humidity
From the psychrometric chart we determine the humidity ratios
We will calculate the volume
From ideal gas equation we will determine the density of outside air
mass flow rate of air entering the room given ACH = 1.32
enthalpy at room temperature Tr ==>
sensible
latent
Total heat transfer